FlexPower Generation 2 DC Power System Installation Manual
6
7
Installation and Operation
1 .4 Typical Installation & Wire Routing
The drawing above shows a typical installation .
Actual configuration and wire routing will vary based on
the components installed in your system .
The following guidelines should be followed for installation:
• Class 2 Power limited wiring must be separated from
non-power limited wiring by a minimum of 1/4 inch and
must use separate knockouts .
• The installation and all wiring methods shall be in accor-
dance with ANSI/NFPA70 and all local codes .
• The installation and all wiring methods shall be in accor-
dance with ANSI/NFPA70 and all local codes . For ULC
S527 compliance, installation and all wiring methods shall
be in accordance with the Canadian Electrical Code, C22 .1,
Part I, Section 32 .
• Any wiring passing through knockouts in the bottom or
top surfaces of the enclosure must be enclosed in rigid
or flexible metal conduit .
• For
Canadian Installations
- For permanently connected
equipment, a readily accessible disconnect device shall be
incorporated external to the equipment . Output circuits
not connected to removable terminal strips shall also
utilize a readily accessible disconnect device .
AC Input Wiring
AC Input Wiring
Class
2
Class
2
FPO75
FPO150
FPO250