background image

15

The Integrated HVAC System

WARNING: The 2500 is a quiet, efficient, low
pressure system.  Special care and attention
should be given if connecting this unit to any
other air handler that may draw more air than
the 2500 is designed to accommodate.

The HRV has become an integral component of the
HVAC system.  Figure 4 shows an HRV unit provid-
ing fresh air directly to the return air plenum of a
Rooftop heat/cool unit.

Many buildings have a ceiling return air plenum 
as in Figure 5.  Fresh air from the HRV can be intro-
duced directly into the ceiling space near the air
handler’s intake.

In installations where it is satisfactory to provide
general exhaust from the space, the air to be
exhausted may be taken directly from the return air
plenum to the HRV as it is drawn back to the air
handler.  Fresh air supplied by the HRV is then intro-
duced directly into the return air plenum but at a
location closer to the air handler.  The air handler
would have a constant running blower to effectively
distribute the fresh air and remove the stale air.
Balancing dampers would be located in both the
HRV supply and exhaust ducts between the return
air plenum and the HRV.   

Electrical Connections

System is 208/230V, 1 phase, 60 Hz.  This unit
meets all local codes and requirements.

It is STRONGLY recommended that an electrical
disconnect be installed prior to the HRV, and that it
is turned off and locked out before servicing the
unit.

All electrical connections should be made by a 
qualified electrician.

Two (2) knock-outs are provided.  One is to be used
for line voltage, and the other one for 24V control
wires.

Maintenance

As with any mechanical system, a dedicated 
maintenance program will prolong the life of the
equipment, and maintain its optimum performance.

We recommend at least two (2) full inspections and
cleanings per year under nor mal operating 
conditions, and more if circumstances warrant it.

Service should include:

•  Cleaning of screens protecting outside hoods.

•  Cleaning of core.

To access core, remove service panels and 
slide core halfway out. Wash core protruding 
from cabinet with water and/or a mild cleaning 
solution. Push core through to the other side of 

the cabinet and repeat procedure to clean the 
other side of the core.  In many cases, only a 
vacuuming of the core surface is required.

•  Inspect filters and replace as necessary.

•  Wipe down drain pans and inside of cabinet,    

using a mild disinfectant.

•  Ensure condensate drain has free flow of 

moisture.

•  Inspect blowers and electrical panel.

•  Confirm operation.

Summary of Contents for 2500EFD

Page 1: ...nstallation the compatibility of the two pieces of equipment must be confirmed by measuring the airflow s of the Heat Recovery Ventilator HRV Energy Recovery Ventilator ERV by using the balancing proc...

Page 2: ...will help in cooling the incoming fresh air with the stale air that is being exhausted Table of Contents Introduction 2 Select Correct HRV 3 Specifications Model 2500IFD 4 Specifications Model 2500EF...

Page 3: ...required 45 x 20 900 cfm 450 L s Bank Customers 25 Staff 9 Total 34 ASHRAE requirement 20 cfm 10 L s per person Ventilation required 34 x 20 680 cfm 320 L s Bar or Tavern Seats 50 Employees 7 Total 5...

Page 4: ...n each air stream DUCT CONNECTIONS Four 24 X 16 610mm X 406mm CABINET 20 gauge powder coated galvanized steel G60 for superior corrosion resistance 16 gauge galvanized frame insulated with1 5 fibregla...

Page 5: ...ar aluminum sensible heat recovery core Plate to plate type Slides out of either side of cabinet for service MOTORS Two single shaft PSC 3 speed 208 230V 5 1 amps 1 ph 1 hp BLOWERS Two direct drive ce...

Page 6: ...ANK TIMER Mechanical timer to activate high speed 99 116 DEHUMIDISTAT VENTILATION CONTROL DVC Turns unit on off via slider switch and high low via built in dehumidistat 99 130 DEHUMIDISTAT Activates h...

Page 7: ...used to control the unit see pg 9 Installation Tips 1 Whichever method is chosen to operate the 2500 keep in mind that Air to Air exchangers in general are not booster fans and are normally sized to v...

Page 8: ...humidity level exceeds selected setting PART NO 99 130 CRANK TIMER Provides high speed ventilation as required Crank Timer 60 minute PART NO 99 101 ON OFF HIGH LOW COMMON I I I I I I I I I I I I I I I...

Page 9: ...e where the surrounding air temperature does not fall below freezing point The exhaust air temperature must be above 60 F 16 C for proper defrost operation If the air temperature is too low the defros...

Page 10: ...n and slope of drain lines Vibration isolators May be anchored to floor leaving space for drain connections 2500IFD Saddle mount not provided Hang unit with threaded rods and U channel members 2 X 4 u...

Page 11: ...RAME To ensure proper mating with unit it is critical that mounting frame be squared to the roof as follows 1 With frame situated level in desired location on roof trusses tack weld one corner of fram...

Page 12: ...elsewhere and provided by the contractor The 2500EFD has built in screens to prevent foreign objects from entering into the ductwork through the out side hoods NOTE It is extremely important to desig...

Page 13: ...grilles should be located high on the wall If contaminants are heavier than air a lower placement of the grilles will be required Information on a contaminants specific gravity and toxicity should be...

Page 14: ...wnstream of any elbows or bends and one foot upstream of any elbows or bends These are recommended distances but the actual installation may limit the amount of straight duct The Pitot tube should be...

Page 15: ...d the HRV Electrical Connections System is 208 230V 1 phase 60 Hz This unit meets all local codes and requirements It is STRONGLY recommended that an electrical disconnect be installed prior to the HR...

Page 16: ...UNIT Check design static pressure of air handler to ensure it is compatible with HRV B A ROOFTOP HEAT COOL UNIT SUPPLY DUCTWORK CEILING RETURN AIR PLENUM ROOF DECK STALE AIR EXHAUST HRV FRESH AIR SUP...

Page 17: ...LOW TIMER ON OFF ON OFF 24V F1 XFRM1 240V 240 VAC 15 AMPS COMMON 24 VAC 24 VAC TI 109 07 97 5 AMP COMMON HIGH LOW HIGH LOW SNAP DISK C3 HIGH BLACK HIGH YELLOW COM BLUE MID RED LOW EXHAUST MOTOR EXHAU...

Page 18: ...5A 5A ON OFF HIGH LOW SNAP DISK TM1 1 R2 1 R1 1 R3 1 R4 1 R3 1 R3 1 R3 1 Blk High Red Low Blk High Red Low Yel Com Yel Com Yel Com Yel Com XFMRI SM SM EM EM Exhaust Motor SM Supply Motor EM R2 R3 R1 R...

Page 19: ...d London Ontario N5W 4C8 519 457 1904 or fax 519 457 1676 to find the name of your nearest dealer in order to repair the product The labour required to install any replacement part s shall be dealt wi...

Page 20: ......

Reviews: