background image

12

Drains

Connect the stainless steel drain pans in the bottom of
the HRV to a drain line fastened to the holes provided.
See pg.10 for location of the drain pans and the drain
connections.  Create a "P" trap to prevent odours from
being drawn through.  Make sure the drain line slopes
down to drain properly and if this is not possible a con-
densate pump will be required for removal of the water.
Note that stagnant water is a leading cause of indoor
air quality problems; confirm drainage after installation
by pouring water into trays. Drain line must be installed
where it will not freeze.

The Ductwork System

A well designed ducting system will allow the HRV to
operate at its maximum efficiency.  Avoid the use of
undersized ducting and sharp radius bends and tees
which can significantly increase the system pressure
drop and reduce the air flows.  

NOTE:  

Fully insulated ducting with an integral vapour 
barrier must be used on all runs passing 
through unheated areas in order to avoid
condensation problems and energy losses 
from the air streams.

* Consult local Codes

To minimize pressure drop and noise, galvanized metal
ducts sized for 1200 fpm (6.09 m/s). (maximum 
velocity)  are recommended.  Keep ducting as short as
possible and use a minimum of elbows and tees.
Connecting sections and shorter runs may be  flexible
ducting one size larger than the metal duct.  Use 
flexible duct connectors 
at the HRV to avoid noise
transmission.

All duct joints must be secured with screws,  rivets or
duct sealant and sealed with aluminum duct tape to
prevent leakage.

Outside Weatherhoods

The 2500EFD is shipped with 2 weatherhoods inside
the cabinet which attach to the outer ends of the cabi-
net using bolts provided. The 2500IFD requires hoods
to be built elsewhere and provided by the contractor.

The 2500EFD has built-in screens to prevent foreign

objects from entering into the ductwork through the out-
side hoods.

NOTE: It is extremely important to design and install
the fresh air intake in an area where the hoods will
gather the freshest air, free from restriction.
Recommended:

• no less than 10 ft. (3 m) apart from each other
• at least 18 in. (46 cm) above ground level
• away from sources of contaminants, such as

automobile exhaust fumes, gas meters, 
garbage containers, cooling towers, etc.

• not exposed to prevailing winds, whenever 

reasonably possible.

The outside perimeter of the weatherhood must be
caulked to prevent leakage into the building.

The design and size of the weatherhoods or louvers
chosen by the installer must allow for adequate free
area. Water and snow penetration of the system is min-
imized when the airflow does not exceed 750 FPM
(3.81m/s) free area velocity.

Ducting from the Weatherhoods

Galvanized sheet metal ducting with sufficient cross
section with an integral single piece vapour barrier
should be used to connect the HRV to the weather-
hoods.  All ducting must meet ULC Class 1 Fire Rating.

minimum R value of insulation should be equal to 4
(RSI 0.75), or as stated in local codes.

A good bead of high quality caulking (preferably
acoustical sealant) and taping with a high quality alu-
minum foil tape is recommended to seal the duct to
both the HRV and the weatherhood.

Warmside Ducting - 

General

Ducting from the HRV to different areas within the
building should be galvanized metal whenever 
possible.

To minimize airflow losses in the ductwork system, all
ducts should be as short as possible and with as few
bends or elbows as possible. 45˚ elbows are preferred
to 90˚ elbows, whenever possible.  Use Y tees instead
of 90˚ tees whenever possible.

All duct joints must be fastened securely and wrapped
with a quality duct tape to prevent leakage.  We recom-
mend aluminum foil tape.

Summary of Contents for 2500EFD

Page 1: ...nstallation the compatibility of the two pieces of equipment must be confirmed by measuring the airflow s of the Heat Recovery Ventilator HRV Energy Recovery Ventilator ERV by using the balancing proc...

Page 2: ...will help in cooling the incoming fresh air with the stale air that is being exhausted Table of Contents Introduction 2 Select Correct HRV 3 Specifications Model 2500IFD 4 Specifications Model 2500EF...

Page 3: ...required 45 x 20 900 cfm 450 L s Bank Customers 25 Staff 9 Total 34 ASHRAE requirement 20 cfm 10 L s per person Ventilation required 34 x 20 680 cfm 320 L s Bar or Tavern Seats 50 Employees 7 Total 5...

Page 4: ...n each air stream DUCT CONNECTIONS Four 24 X 16 610mm X 406mm CABINET 20 gauge powder coated galvanized steel G60 for superior corrosion resistance 16 gauge galvanized frame insulated with1 5 fibregla...

Page 5: ...ar aluminum sensible heat recovery core Plate to plate type Slides out of either side of cabinet for service MOTORS Two single shaft PSC 3 speed 208 230V 5 1 amps 1 ph 1 hp BLOWERS Two direct drive ce...

Page 6: ...ANK TIMER Mechanical timer to activate high speed 99 116 DEHUMIDISTAT VENTILATION CONTROL DVC Turns unit on off via slider switch and high low via built in dehumidistat 99 130 DEHUMIDISTAT Activates h...

Page 7: ...used to control the unit see pg 9 Installation Tips 1 Whichever method is chosen to operate the 2500 keep in mind that Air to Air exchangers in general are not booster fans and are normally sized to v...

Page 8: ...humidity level exceeds selected setting PART NO 99 130 CRANK TIMER Provides high speed ventilation as required Crank Timer 60 minute PART NO 99 101 ON OFF HIGH LOW COMMON I I I I I I I I I I I I I I I...

Page 9: ...e where the surrounding air temperature does not fall below freezing point The exhaust air temperature must be above 60 F 16 C for proper defrost operation If the air temperature is too low the defros...

Page 10: ...n and slope of drain lines Vibration isolators May be anchored to floor leaving space for drain connections 2500IFD Saddle mount not provided Hang unit with threaded rods and U channel members 2 X 4 u...

Page 11: ...RAME To ensure proper mating with unit it is critical that mounting frame be squared to the roof as follows 1 With frame situated level in desired location on roof trusses tack weld one corner of fram...

Page 12: ...elsewhere and provided by the contractor The 2500EFD has built in screens to prevent foreign objects from entering into the ductwork through the out side hoods NOTE It is extremely important to desig...

Page 13: ...grilles should be located high on the wall If contaminants are heavier than air a lower placement of the grilles will be required Information on a contaminants specific gravity and toxicity should be...

Page 14: ...wnstream of any elbows or bends and one foot upstream of any elbows or bends These are recommended distances but the actual installation may limit the amount of straight duct The Pitot tube should be...

Page 15: ...d the HRV Electrical Connections System is 208 230V 1 phase 60 Hz This unit meets all local codes and requirements It is STRONGLY recommended that an electrical disconnect be installed prior to the HR...

Page 16: ...UNIT Check design static pressure of air handler to ensure it is compatible with HRV B A ROOFTOP HEAT COOL UNIT SUPPLY DUCTWORK CEILING RETURN AIR PLENUM ROOF DECK STALE AIR EXHAUST HRV FRESH AIR SUP...

Page 17: ...LOW TIMER ON OFF ON OFF 24V F1 XFRM1 240V 240 VAC 15 AMPS COMMON 24 VAC 24 VAC TI 109 07 97 5 AMP COMMON HIGH LOW HIGH LOW SNAP DISK C3 HIGH BLACK HIGH YELLOW COM BLUE MID RED LOW EXHAUST MOTOR EXHAU...

Page 18: ...5A 5A ON OFF HIGH LOW SNAP DISK TM1 1 R2 1 R1 1 R3 1 R4 1 R3 1 R3 1 R3 1 Blk High Red Low Blk High Red Low Yel Com Yel Com Yel Com Yel Com XFMRI SM SM EM EM Exhaust Motor SM Supply Motor EM R2 R3 R1 R...

Page 19: ...d London Ontario N5W 4C8 519 457 1904 or fax 519 457 1676 to find the name of your nearest dealer in order to repair the product The labour required to install any replacement part s shall be dealt wi...

Page 20: ......

Reviews: