Wiring Inspection
28
9.0
W
IRING
I
NSPECTION
1. Verify all power connections are tightened per the torque specifications in
Table 3
.
2. Verify all control wire terminations are tight.
3. Verify all power wires and connections have proper spacing between exposed surfaces, phase-to-
phase and phase-to-ground.
4. Verify that all control wires are run in steel conduit, separate from all power wiring.
Use 75°C copper wire. Select wire size based on the ampacities in
Table 5
of this manual, a reprint of
Table 310-16 and associated notes of the National Electrical Code (NFPA 70).
Use commercially available solderless lugs for the wire size required for your application. Refer to
Table 3
. Connect wire to the lug using tools and procedures specified by the lug manufacturer.
Table 2
Power wiring terminals, factory supplied
UPS Module Rating
Connection Type
100-225kVA
For “SpaceSaver” modules in the 48" frame, rectifier and bypass inputs are top-entry,
directly to lugs on top of their respective circuit breakers. DC link and critical bus output
connection are top-entry, to frame-mounted lugs.
Standard modules with top-and-bottom entry have access plates and a wireway on the
right side of the modules. All power connections are to busbars in the wireway.
Table 3
Torque specifications
NUT AND BOLT COMBINATIONS
Bolt Shaft Size
Grade 2 Standard
Electrical Connections
with Belleville Washers
Lb-in
N-m
Lb-in
N-m
1/4
53
6.0
46
5.2
5/16
107
12
60
6.8
3/8
192
22
95
11
1/2
428
22
256
29
CIRCUIT BREAKERS WITH COMPRESSION LUGS (FOR POWER WIRING)
Wire Size or Range
Lb-in
N-m
#6 - #4
100
11
#3 - #1
125
14
1/0 - 2/0
150
17
3/0 - 200 MCM
200
23
250 - 400 MCM
250
28
500 - 700 MCM
300
34
CIRCUIT BREAKERS WITH COMPRESSION LUGS (FOR POWER WIRING)
Current Rating
Lb-in
N-m
400 - 1200 Amps
300.00
34.00
TERMINAL BLOCK COMPRESSION LUGS (FOR CONTROL WIRING)
AWG Wire Size or Range
Lb-in
N-m
#22 -#14
3.5 to 5.3
0.4 to 0.6
NOTE:
Use the values in this table unless the equipment is labeled with a different torque value.
Summary of Contents for SERIES 610
Page 6: ...iv...
Page 45: ...Installation Drawings 39 Figure 20 Battery power pack system 88 797616 03 Rev 08...
Page 46: ...Installation Drawings 40 Figure 21 Battery power pack Size A 88 797616 01 Rev 10...
Page 80: ...Installation Drawings 74...
Page 85: ...Site Planning Data Series 610 100 225kVA Multi Module Systems 79 NOTES...
Page 86: ...Site Planning Data Series 610 100 225kVA Multi Module Systems 80...
Page 87: ......