230V SPECIFICATIONS

ELECTRICAL SPECIFICATION

Model Number

PSPXT450-230

PSPXT700-230

PSPXT1250-230

INPUT

Voltage

230 VAC (197 - 262 VAC)

Frequency

50 Hz ± 4Hz; 60 Hz ± 4Hz

Amperage (maximum)

2.6 A

4.0 A

7.0 A

Phase

12 

φ

2W, Ground

OUTPUT

Power rating

450 VA - 270 W

700 VA - 420 W

1250 VA - 750 W 

Voltage

230 VAC ± 10%

Frequency

50 Hz ± 1Hz; 60 Hz ± 1Hz

Wave form

STEP

Line mode 

105%, 

130% load, 3 minutes to fault

Overload protection

Line mode > 130% load, 7s to fault

Battery mode 

105%, 

120% load, 20s to shutdown

Battery mode > 120% load, 5s to shutdown

BATTERY PARAMETERS

Model Number

PSPXT450-230

PSPXT700-230

PSPXT1250-230

Type

Valve-regulated, nonspillable, lead acid

Quantity x Voltage x

(1) x 12V  x 7 Ah

(1) x 12V  x 9 Ah

(2) x 12V  x 7 Ah

Rating
Approved Battery 

CSB,  Panasonic, BB Battery and Yuasa

Manufacturers:
Transfer Time

2 - 6 ms typical

Operating Back-up time

>10 minutes

Recharge time

8hr up to 90%

DIMENSION AND WEIGHTS

Dimensions wxhxd (mm)

80*176,5*233

80*176,5*233

92*238*283

Net Weight, Kg

3.5

3.6

6.5

Gros Weight, Kg

4.5

4.6

7.9

OPERATING ENVIRONMENT

Operation temperature: 0°C to 40°C
Storage Temperature:

-15°C to 40°C

Operation humidity:

20% to 90%

Summary of Contents for PowerSure Personal XT 1250 VA

Page 1: ...450 700 1250 VA 230V PowerSureTM Personal XT USER MANUAL English Deutsch Fran ais Italiano Espa ol...

Page 2: ...OR OTHER APPLICATIONS Store in safe place if not required at this time 4 This UPS must be earthed at all times during operation Connect only to a mains supply socket outlet with an earth connection A...

Page 3: ...stable cart stand or table Do not place UPS under direct sunlight or close to heat emitting sources Do not place UPS power cord in any area where it may get damaged by heavy objects Follow all warning...

Page 4: ...ovides conditioned power to microcomputers and other sensitive electronic equipment PowerSure OUTPUT Lead acid battery inside the enclosure Blei Akkumulator innerhalb des Gehause INPUT FUSE 250V 5A T...

Page 5: ...0V 50 60Hz 4 0A 1 OUTPUT 230V 50 60Hz 700VA 420W 3 1A MADE IN CHINA Remove from Box Remove Plug from Units and replace in UPS Press ON Button Plug Units s into UPS 110 mm 0 40 C Check for Damage OUTPU...

Page 6: ...EDs of the front panel will light up for 2 seconds The green light up continuously This indicates normal operation Note If the UPS continues to beeps or the green light is not alight even mains power...

Page 7: ...c 1 beep every 4 sec Power failure UPS is battery mode 1 beep every sec Battery low UPS is in battery mode batteries are nearly axhausted and UPS will be shut down 1 beep every 2 sec Battery weak UPS...

Page 8: ...n Power cord defective Please contact your dealer Plug the UPS into a working wall outlet for at least Grenn LED blinks very low battery voltage 8 hours to recharge the batteries If the problem red LE...

Page 9: ...itter 8 AC Fail open emitter 9 AC Fail open collector The DB 9 communication port allows the status of UPS to be monitored data to be backed up computer to be switched off COMMUNICATIONS The PowerSure...

Page 10: ...20 load 20s to shutdown Battery mode 120 load 5s to shutdown BATTERY PARAMETERS Model Number PSPXT450 230 PSPXT700 230 PSPXT1250 230 Type Valve regulated nonspillable lead acid Quantity x Voltage x 1...

Page 11: ...ident abuse neglect negligence unauthorized modification alteration or repair use beyond rated capacity or improper installation maintenance application or use including without limitation use in a ma...

Page 12: ...han 1000 kVA Integrated systems that provide both environmental and power protection in a single flexible package Monitoring and control on site or remote from systems of any size or location Service...

Reviews: