Event Message Help Text
127
S2 FAIL
Source 2 Failure
Source 2 has failed due to under voltage (UV), over voltage (OV), or running with an over or under frequency (OF/UF).
This alarm is a companion to S2 UV, S2 UV (RMS), S2 OV and S2 OF/UF.
The load of the STS2 has been transferred to Source 1.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the STS2 system
from a terminal, type
SH
and press RETURN on your keyboard to turn off the audible alarm.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type
CA
and
press RETURN on your keyboard.
S1 OVERCURRENT
Source 1 Overcurrent
STS2 is running on Source 1 and an overload condition has occurred on one or more phases.
Note: The overload setpoint is a single fixed number--101%. An overload condition is detected when the measured load
current is equal to or greater than the setpoint.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the STS2 system
from a terminal, type
SH
and press RETURN on your keyboard to turn off the audible alarm.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type
CA
and
press RETURN on your keyboard.
S2 OVERCURRENT
Source 1 Overcurrent
STS2 is running on Source 2 and an overload condition has occurred on one or more phases.
Note: The overload setpoint is a single fixed number--101%. An overload condition is detected when the measured load
current is equal to or greater than the setpoint.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the STS2 system
from a terminal, type
SH
and press RETURN on your keyboard to turn off the audible alarm.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal, type
CA
and
press RETURN on your keyboard.
Summary of Contents for POWER PROTECTION STATIC TRANSFER SWITCH
Page 1: ...POWER PROTECTION STATIC TRANSFER SWITCH 2 USER MANUAL 100 1000 Amp 50 60 Hz...
Page 2: ......
Page 148: ...Maintenance 140 Channel 8 Channel 9 Channel 10 PRB Notes...
Page 150: ...Maintenance 142...
Page 151: ......