Specifications
114
15.2.9 RS-232 Port
The unit is equipped with an RS-232 port for connecting a terminal or PC.
See
Figure 29
for the port’s location.
See
12.1 - Using the RS-232 Port
for instructions on using a PC terminal with the unit.
15.2.10Terminal Port Connections
The system has an asynchronous serial port configured as Data Terminal Equipment for terminal
access only (half duplex). The CPU services the terminal port with no handshaking. The serial port
conforms to RS-232 levels with a data format of 9600 Baud, 1 start bit, 8 data bits, and no parity bits.
The serial port is 1000 Volt DC isolated (non-SELV) and ESD protected to 15kV air discharge. The
connector is a 6 Pin MTA plug with connections shown below.
A DB9 male connector is added and connected parallel to the 6 position header. It is configured as
DTE.
Table 22
MTA Plug Pinout
Pin
Signal Name
Function / Comments
1
ISO_GND
Isolated service terminal ground
2
ISO_TXD
Isolated service terminal transmit output
3
ISO_RXD
Isolated service terminal receive input
4 NC
No
Connection
5 NC
No
Connection
6 NC
No
Connection
Table 23
DB9 Pinout
Pin
Signal Name
Function / Comments
1 NC
No
Connection
2
ISO_RXD
Isolated service terminal transmit output
3
ISO_TXD
Isolated service terminal receive input
4 NC
No
Connection
5
ISO_GND
Isolated service terminal ground
6 NC
No
Connection
7 NC
No
Connection
8 NC
No
Connection
9 NC
No
Connection
Summary of Contents for POWER PROTECTION STATIC TRANSFER SWITCH
Page 1: ...POWER PROTECTION STATIC TRANSFER SWITCH 2 USER MANUAL 100 1000 Amp 50 60 Hz...
Page 2: ......
Page 148: ...Maintenance 140 Channel 8 Channel 9 Channel 10 PRB Notes...
Page 150: ...Maintenance 142...
Page 151: ......