background image

22 

 

 

4. Trouble Shooting 

If the UPS system does not operate correctly, please solve the problem by using the table below.   

Symptom 

Possible cause 

Remedy 

No  indication  and  alarm  in  the  front 
display panel even though the mains is 
normal.   

The  AC  input  power  is  not 
connected well. 

Check  if  input  cable  firmly 
connected to the mains.   

The  icon 

and  the  warning  code 

  flash  on  LCD  display  and  alarm 

beeps every second. 

EPO function is enabled. 

Set the circuit in closed position 
to disable EPO function.   

The  icon 

and 

  flash  on 

LCD  display  and  alarm  beeps  every 
second. 

The  external  or  internal  battery 
is incorrectly connected. 

Check  if  all  batteries  are 
connected well. 

The  icon 

  and

  flash  on 

LCD  display  and  alarm  beeps  twice 
every second. 

UPS is overload.   

Remove  excess  loads  from 
UPS output. 

UPS  is  overloaded.  Devices 
connected  to  the  UPS  are  fed 
directly 

by 

the 

electrical 

network via the Bypass. 

Remove  excess  loads  from 
UPS output. 

After  repetitive  overloads,  the 
UPS  is  locked  in  the  Bypass 
mode.  Connected  devices  are 
fed directly by the mains. 

Remove  excess  loads  from 
UPS  output  first.  Then  shut 
down the UPS and restart it. 

Fault  code  is  shown  as  43.  The  icon 

  lights  on  LCD  display  and 

alarm beeps continuously. 

UPS  is  overload  too  long  and 
becomes  fault.  Then  UPS  shut 
down automatically. 

Remove  excess  loads  from 
UPS output and restart it. 

Fault  code  is  shown  as  14,  the  icon 

  lights  on  LCD  display,  and 

alarm beeps continuously. 

The 

UPS 

shut 

down 

automatically  because  short 
circuit  occurs  on  the  UPS 
output. 

Check  output  wiring  and  if 
connected  devices  are  in  short 
circuit status. 

Fault  code  is  shown  as  1,  2,  3,  4,  11, 
12, 13, 14,1A, 21, 24, 35, 36, 41 ,42or 
43  on  LCD  display  and  alarm  beeps 
continuously. 

A  UPS  internal  fault  has 
occurred. 

There 

are 

two 

possible results: 
1. The load is still supplied, but 
directly  from  AC  power  via 
bypass.   
2.  The  load  is  no  longer 
supplied by power.   

Contact your dealer 

Battery  backup  time  is  shorter  than 
nominal value 

Batteries are not fully charged 

Charge the batteries for at least 

hours 

and 

then 

check 

capacity.  If  the  problem  still 
persists, consult your dealer.   

Batteries defect 

Contact  your  dealer  to  replace 
the battery. 

The  icon 

and 

  flash  on  LCD 

display and alarm beeps every second. 

Fan is locked or not working; or 
the  UPS  temperature  is  too 
high. 

Check fans and notify dealer.   

Summary of Contents for Adapt BX 10K

Page 1: ...Single Phase Online UPS Liebert Adapt BX User Manual 6k 10kVA...

Page 2: ...4 UPS Installation for Parallel System 6 2 5 Software Installation 6 3 Operations 7 3 1 Button Operation 7 3 2 LED Indicators and LCD Panel 7 3 3 Audible Alarm 9 3 4 Single UPS Operation 10 3 5 Parall...

Page 3: ...for ventilation UPS has provided earthed terminal in the final installed system configuration equipotential earth bonding to the external UPS battery cabinets The UPS can be installed only by qualifie...

Page 4: ...000 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5 Level 4 CS IEC EN 61000 4 6 Level 3 Power frequency Magnetic field IEC EN 61000 4 8 Level 3 Low Frequency Signals IEC EN 61000 2 2 W...

Page 5: ...lug One parallel cable only available for parallel model One share current cable only available for parallel model NOTE Before installation please inspect the unit Be sure that nothing inside the pack...

Page 6: ...as its rated current is less than the UPS s maximum input current Otherwise the receptacle may be burned and destroyed 2 Switch off the mains switch in the building before installation 3 Turn off all...

Page 7: ...ry The battery type and voltage may be different If you connect them together it maybe causes the hazard of electric shock or fire Warning Only for long run model Make sure a DC breaker or other prote...

Page 8: ...g to the section 2 3 2 Connect the output wires of each UPS to an output breaker 3 Connect all output breakers to a major output breaker Then this major output breaker will directly connect to the loa...

Page 9: ...button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press t...

Page 10: ...y voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76...

Page 11: ...lt mode Beeping continuously Warning Overload Beeping twice every second No Low battery Beeping once every second Battery unconnected Over charge EPO enable Fan failure Over temperature Charger failur...

Page 12: ...rned on and enter to Battery mode 3 Connect devices to UPS After the UPS is turned on you can connect devices to the UPS 1 Turn on the UPS first and then switch on the devices one by one the LCD panel...

Page 13: ...7 LCD setting section 6 Test the batteries 1 If you need to check the battery status when the UPS is running in AC mode CVCF mode ECO mode you could press the Test button to let the UPS do battery se...

Page 14: ...t off you should remove the cover of maintenance bypass switch on the rear panel and turn the maintenance switch to BPS position first 3 Switch off the input breaker and switch off the battery breaker...

Page 15: ...the parallel models and follow the wiring refer to section 2 3 3 Install the new parallel system refers to the previous section 3 Remove one unit from the parallel system 1 If the bypass is abnormal...

Page 16: ...B Subtract ADD Add ON On OFF Off FBD Not allowed OPN Allow RES Reserved 3 7 LCD Setting There are three parameters to set up the UPS Refer to following diagram Parameter 1 It s for program alternative...

Page 17: ...tput voltage in parameter 3 208 Presents output voltage is 208Vac 220 Presents output voltage is 220Vac 230 Presents output voltage is 230Vac 240 Presents output voltage is 240Vac 02 Output frequency...

Page 18: ...e default value is 110V Parameter 3 Set the acceptable high voltage for bypass Setting range is from 231V to 276V and the default value is 264V 04 Frequency range for bypass Interface Setting Paramete...

Page 19: ...Hz 08 Bypass mode setting Interface Setting Parameter 2 OPN Bypass allowed When selected UPS will run at Bypass mode depending on bypass enabled disabled setting FBD Bypass not allowed When selected i...

Page 20: ...battery 13 Battery voltage adjustment Interface Setting Parameter 2 Select Add or Sub function to adjust battery voltage to real figure Parameter 3 the voltage range is from 0V to 5 7V the default va...

Page 21: ...output for energy saving LCD display CVCF mode Description When input frequency is within 46 to 64Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery...

Page 22: ...ages in LCD panel LCD display 3 9 Fault Code Fault event Fault code Icon Fault event Fault code Icon Bus start failure 01 None Negative power fault 1A None Bus over 02 None Battery SCR short circuited...

Page 23: ...ing twice every second Battery unconnected Beeping every second Over charge Beeping every second EPO enable Beeping every second Fan failure Over temperature Beeping every second Charger failure Beepi...

Page 24: ...oads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overload too long and becomes fault Then U...

Page 25: ...required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and...

Page 26: ...2 A 10 max Charging Voltage 13 65 V 1 Long run Model Type Depending on applications Numbers 16 20 Charging Current 4 A 10 max 4 A 10 max Charging Voltage 13 65 V 1 PHYSICAL Standard Model Dimension DX...

Page 27: ...25...

Reviews: