2

IMPORTANT SAFETY INSTRUCTIONS

WARNING:  Do not attempt to service this product yourself except to replace

the battery.  Opening or removing the cover may expose you to dangerous
voltages, even when the AC cord is disconnected from the electrical outlet.

Refer all servicing to qualified service personnel.

1. SAVE THESE INSTRUCTIONS. THIS MANUAL CONTAINS IMPORTANT

SAFETY INSTRUCTIONS.  Read all safety and operating instructions before
operating the Uninterruptible Power System (UPS). Adhere to all warnings
on the unit and in this manual. Follow all operating and user instructions.

 

2. This product is designed for Commercial/Industrial use only. It is not

intended for use with life support and other designated “critical” devices.
Maximum load must not exceed that shown on the UPS rating label.  If
uncertain, consult your dealer. See Limited Warranty.

 

3. WHEN REPLACING THE BATTERIES, USE THE APPROPRIATE

LIEBERT-APPROVED REPLACEMENT BATTERY KIT. PROPER
DISPOSAL OF BATTERIES IS REQUIRED.  REFER TO YOUR LOCAL
LAWS AND REGULATIONS FOR DISPOSAL REQUIREMENTS.

 

4. Always turn off the UPS and unplug it before starting the battery

replacement procedure.  To replace batteries, refer to the battery
replacement procedure.  If you feel unqualified to replace the batteries, do
not open the battery door. Refer all servicing to qualified service personnel.

 

5. CAUTION: Do not open or mutilate the batteries.  Released electrolyte is

harmful to skin and eyes and may be toxic.

 

6. The mains supply socket or means of isolation must be within 2 meters of

the equipment and accessible to the operator.  The UPS is designed for data
processing equipment.

 

7. The UPS comes with two output power leads with molded connectors - do

not modify these leads.  Consult dealer if connector does not match the load
socket.  UPS must be grounded at all times while in use.  Turn UPS off
before unplugging it, or the safety earth will be removed.

 

8. The UPStation GXT™ models 700 VA, 1000 VA, 1500 VA, and 2000 VA are

not supplied with an input power lead for connection to the mains supply
socket.  Use the input mains supply power lead from your data processing
equipment to connect the UPS to the mains supply.  For the 3000 VA model,
use the supplied 16 ampere rated input mains supply lead.  For UK supply
systems, consult a qualified electrician to connect the lead supplied for the
3000 VA model to the mains supply.

 

 

CAUTION:  The UPS and the connected load combined total earth leakage
current must not exceed 3.5 milliamperes.  If the connected load earth
leakage current is likely to exceed 2.0 milliamperes or you are unsure, then
convert the input lead attachment to either a fixed wiring installation or an
industrial plug/socket (e.g. CEE 17 connector).  This task should be carried
out by a competent electrical engineer who is conversant with local electrical
codes/regulations.

 

Summary of Contents for 700-3000 VA

Page 1: ...USER MANUAL English Deutsch Fran ais Italiano Espa ol R 700 3000 VA 230V UPStation GXT...

Page 2: ...ed service personnel 5 CAUTION Do not open or mutilate the batteries Released electrolyte is harmful to skin and eyes and may be toxic 6 The mains supply socket or means of isolation must be within 2...

Page 3: ...ded cable for the external communications interface 12 Operate UPS only from a properly earthed 50 Hz or 60 Hz 208 240 VAC mains supply Models are available for 100 127 VAC supply voltages 13 Route po...

Page 4: ...ctronic equipment operates best from sinewave power For ease of use the UPStation GXT contains a light emitting diode LED display to indicate either load percentage or battery capacity depending upon...

Page 5: ...ting this sinewave input current achieves two objectives the mains power is used as efficiently as possible by the UPS and the amount of distortion reflected on the mains is reduced This results in cl...

Page 6: ...ated to indicate the diagnosed problem To manually transfer the connected load from the inverter to bypass power press the Off button once NOTE The bypass power path does NOT protect the connected equ...

Page 7: ...ins lead are colored with the following code Green and Yellow Earth Blue Neutral Brown Live As the color of the wires in the mains lead may not correspond with the colored marking identifying the term...

Page 8: ...screws from the two front feet NOTE The rubber feet are not used for rack mount installations 6 Locate securing flanges in the top of packing material and fasten to the UPS using the flange screws fro...

Page 9: ...arts To isolate the UPS provide an isolator that is accessible to the operator and located within two meters of the UPS The wires in the mains lead are colored with the following code Green and Yellow...

Page 10: ...attery cabinet s are heavy see specifications Take proper precautions when lifting or moving them 3 Visually inspect the UPS for freight damage Report damage to the carrier and your dealer 4 Follow th...

Page 11: ...the ferrite bead so that the ferrite bead s case snaps closed with the cable routed inside the ferrite bead s case SNMP Installation Attach the larger enclosed ferrite bead clamp to the network cable...

Page 12: ...Indicator Load Battery Level Indicators 700 1000 VA Mini Tower 1000 1500 VA Rack Tower 2000 VA Rack Tower 3000 VA Rack Tower 2 6 4 5 3 1 1 6 2 4 6 6 2 2 4 4 3 5 7 7 7 3 5 3 3 1 Output Receptacles 2 DB...

Page 13: ...nds will result in loss of power to the output sockets and connected loads Perform all necessary shutdown procedures on connected loads before pressing this button twice Load Battery Level Indicators...

Page 14: ...powering connected loads Switch positions for voltages 208 VAC 220 VAC 230 VAC 240 VAC NOTE Setting output voltage to 208 VAC will cause UPS unit to be derated to 90 of the VA and Watt rating listed...

Page 15: ...ses fewer indicators remain illuminated Refer to the Troubleshooting Guide For battery run times refer to the Typical Battery Discharge Curves To increase this time turn off non essential pieces of eq...

Page 16: ...NG The UPStation GXT UPS has the capability of being monitored with stand alone computers network workstations network servers or UNIX hosts via the DB 9 female connector located on the rear of the UP...

Page 17: ...the optional internal Ethernet SNMP card Optional SiteNet SNMP Manager software is available to allow communication through several network management systems Contact your local Liebert representative...

Page 18: ...attery door screws FOR 700 1000 VA MINI TOWER MODELS 1 Gently lay the UPS on its right side 2 Loosen and remove the five screws on the battery door Remove the door by sliding it toward the rear of UPS...

Page 19: ...reassembly 4 Pull battery assembly out approximately 50mm 2 in Gently pull the battery wiring out and disconnect the battery connector 5 Completely remove battery assembly from the UPS 6 Unpack the n...

Page 20: ...EMENT Large battery door Battery connector Large battery door Screw hidden by small battery door Small battery door Two front rubber feet Front bezel cover Rear View Aerial View w top cover removed Fl...

Page 21: ...00RT 10 N A N A 479 552 408 343 273 20 N A N A 255 335 215 204 140 30 N A N A 150 210 126 133 78 40 N A N A 110 152 95 100 57 50 N A N A 85 115 75 77 44 60 N A N A 66 88 57 60 35 70 N A N A 56 72 48 5...

Page 22: ...ocks into position 5 Reconnect the input power lead to the UPS and the input power lead to the input AC supply 6 Restart the UPS The UPS is ready for normal operation NOTE For 1500 VA 2000 VA and 3000...

Page 23: ...All On bypass due to output overload beep every half second A On bypass due to over temperature condition beep every 4 seconds B On bypass due to DC bus overvoltage beep every 4 seconds C On bypass d...

Page 24: ...l display and remove non essential loads Recalculate load VA and reduce number of loads connected to UPS Check load equipment for faults Fault and Bypass indicators and diagnostic LED A are illuminate...

Page 25: ...t Sockets 4 IEC320 10A 4 IEC320 10A Voltage 208 220 230 240 switch selectable VAC 3 Frequency 50 Hz or 60Hz Waveform Sinewave Main Mode Overload 200 for 8 cycles 130 for 10 seconds with transfer to by...

Page 26: ...Output Sockets 4 IEC320 10A 4 IEC320 10A Voltage 208 220 230 240 switch selectable VAC 3 Frequency 50 Hz or 60Hz Waveform Sinewave Main Mode Overload 200 for 8 cycles 130 for 10 seconds with transfer...

Page 27: ...r IEC320 10A IEC320 10A IEC320 16A OUTPUT AC PARAMETERS Output Sockets 4 IEC320 10A 4 IEC320 10A 4 IEC320 10A 1 IEC320 16A Voltage 208 220 230 240 switch selectable VAC 3 Frequency 50 Hz or 60Hz Wavef...

Page 28: ...tr x Batt Voltage x Batt Rating 2x3x12Vx7 0 or 7 2 AH 2x4x12Vx7 0 or 7 2 AH 1x8x12Vx7 0 or 7 2 AH Batt Mfg Part CSB GP1270F2 or Panasonic LC R127R2CH1 Back up Time See Typical Battery Discharge Curves...

Page 29: ...nauthorized modification alteration or repair use beyond rated capacity or improper installation maintenance application or use including without limitation use in a manner contrary to the accompanyin...

Page 30: ...d UPS with power ranges from 250 VA to more than 1000 kVA Integrated systems that provide both environmental and power protection in a single flexible package Monitoring and control on site or remote...

Reviews: