26
SPECIFICATIONS
MODEL NUMBER
GXT1000RT-230
GXT1000RTE-230
MODEL RATING VA/W
1000 / 700
1000 / 700
DIMENSIONS: mm (in)
Unit
W x D x H
177 x 522 x 430
(7.0 x 19.3 x 16.9)
177 x 522 x 430
(7.0 x 19.3 x 16.9)
Shipping
W x D x H
340 x 660 x 565
(13.38 x 26.0 x 22.25)
340 x 660 x 565
(13.38 x 26.0 x 22.25)
WEIGHT: kg (lbs)
Unit
23.6 (51.9)
31.1 (68.4)
Shipping
26.8 (59.0)
34.3 (75.5)
INPUT AC PARAMETERS
Voltage Range (typical)
230 VAC nominal; variable based upon output load
100% - 70% Loading
160-163 VAC to 273-276 VAC
70% - 30% Loading
140-143 VAC to 273-276 VAC
30% - 0% Loading
120-122 VAC to 273-276 VAC
Frequency
48.1 - 51.9 Hz or 57.6 - 62.4 Hz; auto sensing
Input connector
IEC320-10A
IEC320-10A
OUTPUT AC PARAMETERS
Output Sockets
(4) IEC320-10A
(4) IEC320-10A
Voltage
208/220/230/240 (switch selectable) VAC; ±3%
Frequency
50 Hz or 60Hz
Waveform
Sinewave
Main Mode Overload
200% for 8 cycles; 130% for 10 seconds with transfer to bypass
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, lead acid
Qty. x Voltage x Rating
3 x 12V x 7 or 7.2 AH
6 x 12V x 7 AH
Back-up Time
See Typical Battery Discharge Curves
ENVIROMENTAL
Operating Temperature
0° C to +40° C (+32° F to +104° F)
Storage Temperature
-15° C to +50° C (+5° F to +122 °F)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 3000 m (10,000 ft.) at 40° C without derating
Storage Elevation
15.000 m (50,000 ft.) maximum
Audible Noise
<50 dBA, at 1 meter
AGENCY
Safety
EN50091-1, TUV/GS Listed, CE Low Voltage Directive compliant
RFI/EMI
EN55022, Class B; CE EMC Directive compliant
Immunity
IEC 801-2, Level 4 / IEC 801-3, Level 3 / IEC 801-4, Level 4 / IEC801-
5,Level 3