INSTALLER’S SETTING OPTIONS
203
ENGLISH
202
INSTALLER’S SETTING OPTIONS
●
Press and hold ‘wireless remote controller signal receiver part’ of the remote controller for 3
seconds or longer to enter the installer function.
●
At the Code field, select the indoor unit address verification code value ‘26’.
- You can press ‘
▲
’, ‘
▼
’ button to change the code value.
●
Verify the indoor unit's setting in the Value 1 field, and press ‘Done’ button to complete the in-
door unit address verification.
Indoor unit address verification (air conditioner)
This function allows you to check the address of the indoor unit designated by the outdoor unit.
h
Setting value of each function
- 00: Not installed
- 01: Installed
●
Press and hold ‘wireless remote controller signal receiver part’ of the remote controller for 3
seconds or longer to enter the installer function.
●
At the Code field, select the code value of the desired functional product as shown in the table
below.
- You can press ‘
▲
’, ‘
▼
’ button to change the code value.
●
In the Value 1 field, press the ‘
▲
’, ‘
▼
’ button to select the setting value for each function, and
press ‘Done’ button when complete.
- If you do not press ‘Done’ button, your settings will not be applied.
External Devices Of Indoor Unit Setting (air conditioner)
At the Code field, select when air cleaner/heater/humidifier/elevation grill/ventilation KIT/refrigerant
leakage detection sensor are newly installed to the indoor unit or when an installed KIT is removed.
h
If no buttons are pressed for about 60 seconds after the setting, it automatically exits from the
setting mode.
Function
Code value
Air cleaner
20
Heater
21
Humidifier
22
Elevation grill
23
Ventilation KIT
24
Refrigerant leakage
detection sensor
29