9
THERMA V
Monobloc Type
Design and installation
6. Installation
6.1 Foundation for Installation
• Check the strength and level of the installation ground so that the unit will not cause any operating vibration or
noise after installation.
• Fix the unit securely by means of the foundation bolts.
(Prepare 4sets of M12 foundation bolts,nuts and washers each which are available on the market.)
• It is best to screw in the foundation bolts until their length are 20mm from the foundation surface.
WARNING
• Be sure to remove the Pallet(Wood Support) of the bottom side
of the outdoor unit Base Pan before fixing the bolt. It may cause
the unstable state of the outdoor settlement, and may cause
freezing of the heat exchanger resulting in abnormal operations.
• Be sure to remove the Pallet(Wood Support) of the bottom side
of the outdoor unit before welding. Not removing Pallet(Wood
Support) causes hazard of fire during welding.
Foundation bolt executing method
[Unit:mm]
200
Nut
75
75
200
Spring washer
Frame
Anti-vibration
materials
Six bolt are
required
3 thread ridges
H-Beam
Concrete
base
100
Pallet(Wood Support)
- Remove before Installation