Display
code
Title
Cause of error
Check point & Normal condition
41
Problem in D-pipe temperature sensor
•
Open / Short
•
Soldered poorly
•
Internal circuit error
1.
Bad connection of thermistor connector
2.
Defect of thermistor connector
(Open/Short)
3.
Defect of outdoor PCB(lnverter)
43
Problem in high pressure sensor
Abnormal value of sensor
(Open/Short)
•
Bad connection of connector PCB(lnverter)
•
Bad connection high pressure connector
•
Defect of high pressure connector
(Open/Short)
•
Defect of connector PCB(lnverter)
(Open/Short)
•
Defect of PCB(lnverter)
44
Problem in outdoor air temperature sensor
•
Open / Short
•
Soldered poorly
•
Internal circuit error
1.
Bad connection of thermistor connector
2.
Defect of thermistor connector
(Open/Short)
3.
Defect of outdoor PCB(lnverter)
45
Problem in Cond. middle pipe temperature sensor
•
Open / Short
•
Soldered poorly
•
Internal circuit error
1.
Bad connection of thermistor connector
2.
Defect of thermistor connector
(Open/Short)
3.
Defect of outdoor PCB(lnverter)
46
Problem in suction pipe temperature sensor
•
Open / Short
•
Soldered poorly
•
Internal circuit error
1.
Bad connection of thermistor connector
2.
Defect of thermistor connector
(Open/Short)
3.
Defect of outdoor PCB(lnverter)
52
PCB Communication Error
Checking the communication state
between Main PCB and Inverter PCB
•
Generation of noise
source interfering with
communication
32
High temperature in Discharge pipe of the
inverter compressor
•
Overload operation (Outdoor fan
constraint, screened, blocked)
•
Refrigerant leakage (insufficient)
•
Poor INV Comp Discharge sensor
•
LEV connector displaced/ poor
LEV assembly
•
Check outdoor fan constraint/
screened/ flow structure
•
Check refrigerant leakage
•
Check if the sensor is normal
•
Check the status of EEV assembly
35
Low pressure Error
Excessive decrease of low pressure
•
Defective low pressure sensor
•
Defective unit fan
•
Refrigerant shortage/leakage
•
Deformation because of damage of
refrigerant pipe
•
Defective unit EEV
•
Covering/ clogging (unit
covering during the cooling
mode/ unit filter clogging during
heating mode)
•
SVC
valve
clogging
•
Defective unit PCB(lnverter)
•
Defective unit pipe sensor