T: 0191 516 6554
Here We Talk about setting the Weather Compensated Curve in Installer settings.
(*These Setting will be site Dependant)
In the example below the external design temp is -2.8
֯
C with a Design Flow temp of 50
֯
C for Radiators
LG Therma V R32 Monobloc Installer Setting Guide - Bing video
Function
Description
Range
Default
Set
Outdoor 1, Heat
(OUT 1)
Heating Lower ambient
Temp
-25 - 35
֯
c
-10
֯
c
- 2.8
֯
c *
Outdoor 2, Heat
(OUT 2)
Heating Higher ambient
Temp
16
֯
c
19
֯
c *
Water1, Heat
(LW1)
Heating higher Water Temp
Dependant on Field Settings
35
֯
c
50
֯
c *
Water2, Heat
(LW2)
Heating Lower Water Temp
28
֯
c
30
֯
c *
MODE- Select HEAT