- 67 -
60
PCB(Inverter) & Main
EEPROM check sum error
EEPROM Access error
and Check SUM error
1. EEPROM contact defect/wrong insertion
2. Different EEPROM Version
3. ODU Inverter & Main PCB assembly 1 damage
Display
code
Title
Cause of error
Check point & Normal condition
n
Error Diagnosis and Countermeasure Flow Chart
Is EEPROM insertion normal?
No
Yes
Recheck power and installation condition
1.Check EEPROM insert direction/connection condition
2.Check EEPROM Check SUM
→
Replace if abnormality found
Is PCB assembly 1 normal?
No
Yes
Replace PCB assembly 1
Yes
MAIN PCB assembly 1 normal?
No
Replace MAIN PCB assembly 1
WARNING
Before checking PCB(Inverter) or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby
state of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Check Point
- Check the EEPROM Check sum & Direction
▶
AHUW096A3
Summary of Contents for THERMA V AHNW16606B0
Page 16: ... 16 6 Wiring Diagrams Indoor Unit Model AHNW16606B0 ...
Page 18: ... 18 Outdoor Unit Models AHUW146A2 Models AHUW096A3 ...
Page 19: ... 19 Models AHUW166A3 AHUW146A3 AHUW126A3 ...
Page 20: ... 20 Models AHUW168A3 AHUW148A3 AHUW128A3 ...
Page 50: ... 50 Vdc P GND AHUW146A2 AHUW126A3 AHUW146A3 AHUW166A3 AHUW128A3 AHUW148A3 AHUW168A3 ...
Page 56: ... 56 P T S R N U N V N W AHUW128A3 AHUW148A3 AHUW168A3 ...
Page 68: ... 68 EEPROM EEPROM AHUW146A2 AHUW126A3 AHUW146A3 AHUW166A3 AHUW128A3 AHUW148A3 AHUW168A3 ...
Page 76: ... 76 L N N L L L N N N L N L L N AHUW146A2 AHUW126A3 AHUW146A3 AHUW166A3 ...
Page 77: ... 77 L N L N R S T N L N L N AHUW128A3 AHUW148A3 AHUW168A3 ...
Page 81: ......