- 36 -
Displaying the error
MODULE 2 - ALARM
Description of error
Failure of module 2
Response of internal unit
controller
The device automatically restarts after the error is resolved
Possible causes
• The wiring of the expansion relay panel of module 2 is damaged or not implemented correctly.
• The expansion relay panel of module 2 is damaged or defective:
Troubleshooting
1. Turn off power supply and turn it back on. Wait to see if the communication resumes.
2. Error of the module 2 relay panel wiring:
a. Check the wiring of module 2 relay panel according to the electrical wiring scheme. If an error is
found in the wiring, resolve it.
3. The relay panel of module 2 is damaged or defective:
a. Carry out an inspection; in case there is damage or inadequacy, the relay panel of module 2 must
be replaced.
b. Check the user interface if there is communication between PLC, MBIO12.
1
MODULE 2 - ALARM
The reading of the error in the first line of the PLC controller inter-
face. Hold the
key to display
- SERVICE-DISPLAY -
To enter the menu, press the
(ENTER) key.
Hold the
key to display the lower part.
2
MODULE 2. 45 73 Bet:0
Bet:0
– no problems with the connection with MD2
Bet:5
– Bet > 0 means there is no 100% connection between mod-
ules.
Modules not used in the system have a value of
Bet:9
, which
means the modules do not and must not report.
Use keys
and
navigate to other modules.
4. If the module is physically present and reports with
Bet:9
, check the module itself if the signal LED diode
RUN, RX and TX is lit (on newer models it flashes):
RUN
– MBIO12 is operational,
RX. TX
- the signal means there is communication between MBIO12 and PLC
5. Check whether all bridges are on their designated spots (see chapter 2.6.1).
Summary of Contents for THERMA V AHNW16606B0
Page 16: ... 16 6 Wiring Diagrams Indoor Unit Model AHNW16606B0 ...
Page 18: ... 18 Outdoor Unit Models AHUW146A2 Models AHUW096A3 ...
Page 19: ... 19 Models AHUW166A3 AHUW146A3 AHUW126A3 ...
Page 20: ... 20 Models AHUW168A3 AHUW148A3 AHUW128A3 ...
Page 50: ... 50 Vdc P GND AHUW146A2 AHUW126A3 AHUW146A3 AHUW166A3 AHUW128A3 AHUW148A3 AHUW168A3 ...
Page 56: ... 56 P T S R N U N V N W AHUW128A3 AHUW148A3 AHUW168A3 ...
Page 68: ... 68 EEPROM EEPROM AHUW146A2 AHUW126A3 AHUW146A3 AHUW166A3 AHUW128A3 AHUW148A3 AHUW168A3 ...
Page 76: ... 76 L N N L L L N N N L N L L N AHUW146A2 AHUW126A3 AHUW146A3 AHUW166A3 ...
Page 77: ... 77 L N L N R S T N L N L N AHUW128A3 AHUW148A3 AHUW168A3 ...
Page 81: ......