- 49 -
Check Point
1. Check the WCN_P(L),P(N) Connection condition at the main PCB(Heater). (Refer to wiring diagram)
2. Check the DC Link voltage at not operating(280V
)
3. Check the DC Link voltage at Comp operating(340V
)
4. Check DC Link Sensing Signal(AHUW**6A2): 2.4~2.8V (Refer the Picture)
5. Check DC Link Sensing Signal(AHUW**8A2): 0.4~0.6V (Refer the Picture)
’
’
IN/I
GND
<CT Sensing Check Point>
Black
Red
Vdc
* AHUW096A3