- 52 -
27
26
25
24
23 22 21
P
W
V
U
Nw Nv Nu
SPM3
1. Wait PCB DC voltage is discharged after main power off.
2. Pull out V, V, W COMP connector.
3. Set multi tester to resistance mode.
4. If the value between P and N terminal of IPM is short(0Ω) or open(hundreds MΩ), PCB needs to be replaced.(IPM dam-
aged)
5. Set the multi tester to diode mode.
6. In case measured value is different from the table, PCB needs to be replaced. (PCB damaged).
27
26
25
24
23 22 21
P
W
V
U
Nw Nv Nu
P
W
V
U
Nw Nv Nu
0.4 ~ 0.6 V
27
26
25
24
23 22 21
0.4 ~ 0.6 V
PFC_IPM check
U, V, W
‘
R S T
1. IPM Check
Summary of Contents for THERMA V AHNW16606B0