- 75 -
26
DC Compressor
Position
• Compressor
Starting fail error
• Check the connection of comp wire “U,V,W”
• Malfunction of compressor
• Check the component of “IPM”, detection parts.
Display
code
Title
Cause of error
Check point & Normal condition
Is installation
condition normal?
No
Yes
Yes
Recheck power and installation condition
1. Check Pipe clogging/distortion
2. Check Covering (Indoor/Outdoor Unit)
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
→
Reassemble or manage if abnormality found
1. Check resistance between each terminal of compressor
2. Check insulation resistance between compressor
terminal and pipe
→
Replace compressor if abnormality found
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
No
Yes
1. Check inverter PCB assembly U,V,W connector
connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
→
Reassemble if abnormality found
Is compressor
Wire connection
condition normal?
No
Yes
Check inverter PCB assembly IPM normality
→
Replace inverter PCB assembly
Is inverter PCB assembly normal?
No
WARNING
Before checking PCB(Inverter) or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby
state of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
n
Error Diagnosis and Countermeasure Flow Chart
Summary of Contents for THERMA V AHBW076A0
Page 7: ... 7 Part 1 General Information 1 Model Names 8 2 External Appearance 8 3 Nomenclature 9 ...
Page 13: ... 13 Part 2 Features Controls 1 List of Function 11 2 Features Controls 12 3 Test Run 34 ...
Page 46: ... 46 Part 5 Trouble Shooting ...
Page 74: ... 74 Vdc AHBW126A0 AHBW146A0 AHBW166A0 P GND ...
Page 86: ... 86 AHBW126A0 AHBW146A0 AHBW166A0 EEPROM ...
Page 98: ...P NO MFL68026801 October 2013 ...