- 73 -
Check Point
1. Check the WCN_P(L),P(N) Connection condition at the main PCB(Heater). (Refer to wiring diagram)
2. Check the DC Link voltage at not operating(280V
↑
)
3. Check the DC Link voltage at Comp operating(340V
↑
)
4. Check DC Link Sensing Signal :2.4~2.8V (Refer the Picture)
IN/I
GND
<CT Sensing Check Point>
Black
Red
Vdc
* AHBW056A0/AHBW076A0/AHBW096A0