System Set-Up
48
Air-to-Water Heat Pump
Code
Item
Detail
Remark
05
Function
Setting temperature selection
Description
Selection for setting temperature as air temperature or
leaving water temperature.
Value #1
Note
01:Air temperature
02:Leaving water temperature
Air temperature as setting temperature is ONLY available
when remote air sensor.
Connection is enabled and Function code 03 is set as 02.
Default
2
Range
01 ~ 02
Value #2
Note
-
Default
-
Range
-
06
Function
Auto dry contact
Description
Setting dry contact auto start option.
If thermostat is used, value should be changed from "2" to "1".
Value #1
Note
01: Auto start off
02: Auto start on
Default
2
Range
01 ~ 02
Value #2
Note
-
Default
-
Range
-
07
Function
Address setting
Description
Assigning address when central controller is installed
If thermostat is used, value should be changed from "2" to "1".
Value #1
Note
-
Default
00
Range
00 ~ FF
Value #2
Note
-
Default
-
Range
-