6-2 PTC AND OLP
6
5
Shows continuity
Open
Normal operation of
Compressor is
impossible or poor.
Separate PTC-Starter
from Compressor and
measure resistance
between No. 5 and 6
of PTC-Starter with a
Tester.
(Figure 14)
Separate OLP from
Compressor and check
resistance value
between two terminals
of OLP with a Tester.
(Figure 15)
Observation value is
115V/60Hz : 6.8
±30%
The resistance value
is 0
(short) or
(open).
Check another
electric component.
Replace OLP.
Replace PTC-
Starter.
Figure 14
Figure 15