65 Accessories
Controller accessories
6RWU0-03A
PTAC
1. Controller accessories
1.1 Hard Wire Kit
The Hard Wire kit consists of a Junction box which provides a
protective enclosure for the electrical connections. This junc-
tion box is furnished with approximately 2 -
1
/
2
feet of
1
/
2
inch
flexible steel conduit and a metal box that secures to the
PTAC at the control panel. The Hard Wire kit connects the
PTAC directly to the building power supply wires and the
junction box is intended to be mounted on the wall or the floor
near the PTAC.
Installation Procedure:
The Installation and servicing of the equipment should be
performed by qualified and experienced personnel only.
1) At first, remove the cover plate from the junction box.
Then, mount the junction box on the wall or floor within 28
inches (711mm) from the lower right corner of the wall
sleeve so that the metal box is suitably clamped on the
side of the sleeve as shown on the right below.
2) If a power switch is to be used, make sure the electrical
connections are done and then mount the switch onto the
junction box. During this operation, refer to the Power
Switch Installation instructions.
3) Remove the control panel assembly by removing the two
screws holding the control panel in place and then gently
lift the panel. Disconnect the power cord leads from all
electrical connections including the ground wire.
4) Remove the power cord clamp and the power cord from
the unit.
Hardwire Kit
AYHW101
Wall Sleeve
Cover plate
Control Panel
Base Pan
Bracket
Ground Wie
with Eyelet
Terminal
Power Leads
with Push on
Connectors
Metal Box
with Straight Clamp
Conduit
28 Inch es Max