40
BMS PROTOCOL
ENGLISH
Register
Description
Function Code
Value explanation
1
2
3
4
5
6
10027
Reserved
-
-
-
-
-
-
-
10028
Reserved
-
-
-
-
-
-
-
10029
Reserved
-
-
-
-
-
-
-
10030
Reserved
-
-
-
-
-
-
-
30001
Error Code
-
-
-
•
-
-
1xxxx
2)
30002
Reserved
-
-
-
-
-
-
-
30003
Reserved
-
-
-
-
-
-
-
30004
Reserved
-
-
-
-
-
-
-
30005
Reserved
-
-
-
-
-
-
-
30006
Reserved
-
-
-
-
-
-
-
30007
Reserved
-
-
-
-
-
-
-
30008
Reserved
-
-
-
-
-
-
-
30009
Reserved
-
-
-
-
-
-
-
30010
Reserved
-
-
-
-
-
-
-
30011
RA Temp.
-
-
-
•
-
-
-50.0 °C~100.0 °C (x10)
30012
Reserved
-
-
-
-
-
-
-
30013
SA Temp.
-
-
-
•
-
-
-50.0 °C~100.0 °C (x10)
30014
Reserved
-
-
-
-
-
-
-
30015
Reserved
-
-
-
-
-
-
-
30016
Reserved
-
-
-
-
-
-
-
40001
Operation Mode
-
-
•
-
-
•
0: Cooling / 2: Fan / 4: Heating
40002
Capacity
1)
-
-
•
-
-
•
0, 2.0V~10V (x10, 0.5V)
40003
Cooling Target Temp.
-
-
•
-
-
•
16.0 °C~30.0 °C (x10, 1 °C)
40004
Heating Target Temp.
-
-
•
-
-
•
16.0 °C~30.0 °C (x10, 1 °C)
40005
Reserved
-
-
-
-
-
-
-
40006
Reserved
-
-
-
-
-
-
-
40007
Reserved
-
-
-
-
-
-
-
40008
Reserved
-
-
-
-
-
-
-
40009
Reserved
-
-
-
-
-
-
-
40010
Reserved
-
-
-
-
-
-
-
40028
Fan Speed
-
-
•
-
-
•
1 : Low / 2 : Middle / 3 : High
Memory Map
Error Code
Module Number
NOTE
• Regarding capacity ratio, you can refer to the Capacity setting table of UI7(0~10V) of
PAHCMS000.
• Error Code : 1 x xxx
Summary of Contents for PAHCMR000
Page 14: ...14 RETURN AIR TEMPERATURE CONTROL PAHCMR000 ENGLISH Electric Wiring Work PAHCMR000 ...
Page 46: ...46 ENGLISH ...
Page 47: ......