RETURN AIR TEMPERATURE CONTROL (PAHCMR000)
19
ENGLISH
n
Digital Output – Fan Speed (Change)
‘Fan Speed Output (Change)’ is available when DIP SW1-3 is ON and DIP SW1-4 is OFF.
• Cooling or Heating – TH ON
Name
Port
Value
Electrical Spec.
Function
Short
Open
Fan_High
DO1
High
-
250 V AC / 1 A
30 V DC / 1 A
DO ports output fan speed signal
according to setting value
Fan_Mid
DO2
Mid
Fan_Low
DO3
Low
• Cooling – TH OFF
Name
Port
Value
Electrical Spec.
Function
Short
Open
Fan_High
DO1
-
TH OFF
250 V AC / 1 A
30 V DC / 1 A
DO 1,2 is ‘ Open’, DO 3(Low) is ‘short’.
Fan_Mid
DO2
-
TH OFF
Fan_Low
DO3
TH OFF
-
• Heating – TH OFF or defrost
Name
Port
Value
Electrical Spec.
Function
Short
Open
Fan_High
DO1
-
TH OFF
250 V AC / 1 A
30 V DC / 1 A
1) During defrost, All DOs are ‘Open’.
2) The fan speed will be changed
according to TH on/off.
In cooling mode,
- The fan speed will be running as low
fan during TH off.
- The fan speed will be running as set
fan speed during TH on.
In heating mode,
- The fan speed will be stopped during
TH off temperature setting.
- The fan will be running for 20 s during
TH OFF.
- The fan speed will be running as set
fan speed during TH on with pipe
temp.
Fan_Mid
DO2
-
TH OFF
Fan_Low
DO3
-
TH OFF