DISCHARGE AIR TEMPERATURE CONTROL (PAHCMS000)
ENGLISH
n
UI7(Analog Input) – ODU Capacity Control #2
‘ODU Capacity Control #2’ is available when DIP SW2-1 is ON, each Master ODU will have the same
operating ratio according to following tables.
Voltage (V)
ODU Capacity Range (%)
Estimated Eva.
Temp. (Te,°C)
Estimated Cond.
Temp. (Tc,°C)
0.0
Operation OFF
-
-
1.0
100
6.0
49.0
2.0
90
7.0
46.5
3.0
80
8.0
44.0
4.0
70
9.0
41.5
5.0
60
10.5
39.0
6.0
50
12.0
36.5
7.0
45
13.0
35.3
8.0
40
14.0
33.5
9.0
Operation OFF
-
-
10.0
Operation OFF
-
-
<Main Module>
CAUTION
!
Actual temperature at evaporator may varies by pressure drop. Please contact local sale
person to design AHU heat exchanger.
NOTE
• Based on 7.5 m piping length condition, According to piping length evaporating/condensing
temperature will be increasing/decreasing.
• ODU Capacity ratios mentioned in the table above are not exact.
• ‘Evaporative temperature / Condenser temperature’ may vary depending on system operating
frequency, pressure option setting and piping installation conditions.