Outside units Information
Installation Manual
9
ENGLISH
Unit
1 Unit
System Capacity (HP)
18
20
Model
Combination Unit
ARWN180LAS4
ARWN200LAS4
Independent Unit
ARWN180LAS4
ARWN200LAS4
Refrigerant Precharged Amount
kg
3.0
3.0
Maximum Connectable Number of Indoor Units
29
32
Net Weight
kg
140 x 1
140 x 1
lbs
309 x 1
309 x 1
Dimensions(WxHxD)
mm
755 × 997 × 500
755 × 997 × 500
inch
(29-23/32 x 39-1/4 x 19-11/16) x 1
(29-23/32 x 39-1/4 x 19-11/16) x 1
Refrigerant
Connecting Pipes
Liquid
mm(inch)
12.7(1/2)
12.7(1/2)
Gas
mm(inch)
28.58(1-1/8)
28.58(1-1/8)
Water Connecting
Pipes
Inlet
mm
PT 40
PT 40
Outlet
mm
PT 40
PT 40
Drain Outlet
mm
20
20
Temp. range of
Circulation water
Cooling
10°C ~ 45°C(50°F ~ 113°F)
10°C ~ 45°C(50°F ~ 113°F)
Heating
-5°C ~ 45°C(23°F ~ 113°F)
-5°C ~ 45°C(23°F ~ 113°F)
Unit
2 Unit
System Capacity (HP)
22
24
26
Model
Combination Unit
ARWN220LAS4
ARWN240LAS4
ARWN260LAS4
Independent Unit
ARWN120LAS4
ARWN100LAS4
ARWN120LAS4
ARWN120LAS4
ARWN140LAS4
ARWN120LAS4
Refrigerant Precharged Amount
kg
3.5 + 3.4
3.5 + 3.5
5.8 + 3.5
Maximum Connectable Number of Indoor Units
35
39
42
Net Weight
kg
125 x 2
125 x 2
(127 x 1) + (125 x 1)
lbs
276 x 2
276 x 2
(280 x 1) + (276 x 1)
Dimensions(WxHxD)
mm
(755 × 997 × 500) x 2
(755 × 997 × 500) x 2
(755 × 997 × 500) x 2
inch
(29-23/32 x 39-1/4 x 19-11/16) x 2 (29-23/32 x 39-1/4 x 19-11/16) x 2 (29-23/32 x 39-1/4 x 19-11/16) x 2
Refrigerant
Connecting Pipes
Liquid
mm(inch)
19.05(3/4)
19.05(3/4)
19.05(3/4)
Gas
mm(inch)
34.9(1-3/8)
34.9(1-3/8)
34.9(1-3/8)
Water Connecting
Pipes
Inlet
mm
PT 40 + PT 40
PT 40 + PT 40
PT 40 + PT 40
Outlet
mm
PT 40 + PT 40
PT 40 + PT 40
PT 40 + PT 40
Drain Outlet
mm
20
20
20
Temp. range of
Circulation water
Cooling
10°C ~ 45°C(50°F ~ 113°F) 10°C ~ 45°C(50°F ~ 113°F) 10°C ~ 45°C(50°F ~ 113°F)
Heating
-5°C ~ 45°C(23°F ~ 113°F)
-5°C ~ 45°C(23°F ~ 113°F)
-5°C ~ 45°C(23°F ~ 113°F)
Unit
2 Unit
System Capacity (HP)
28
30
32
Model
Combination Unit
ARWN280LAS4
ARWN300LAS4
ARWN320LAS4
Independent Unit
ARWN140LAS4
ARWN140LAS4
ARWN160LAS4
ARWN140LAS4
ARWN180LAS4
ARWN140LAS4
Refrigerant Precharged Amount
kg
5.8 + 5.8
3.0 + 5.8
3.0 + 5.8
Maximum Connectable Number of Indoor Units
45
49
52
Net Weight
kg
127 x 2
(140 x 1) + (127 x 1)
(140 x 1) + (127 x 1)
lbs
280 x 2
(309 x 1) + (280 x 1)
(309 x 1) + (280 x 1)
Dimensions(WxHxD)
mm
(755 × 997 × 500) x 2
(755 × 997 × 500) x 2
(755 × 997 × 500) x 2
inch
(29-23/32 x 39-1/4 x 19-11/16) x 2 (29-23/32 x 39-1/4 x 19-11/16) x 2 (29-23/32 x 39-1/4 x 19-11/16) x 2
Refrigerant
Connecting Pipes
Liquid
mm(inch)
19.05(3/4)
19.05(3/4)
19.05(3/4)
Gas
mm(inch)
34.9(1-3/8)
34.9(1-3/8)
34.9(1-3/8)
Water Connecting
Pipes
Inlet
mm
PT 40 + PT 40
PT 40 + PT 40
PT 40 + PT 40
Outlet
mm
PT 40 + PT 40
PT 40 + PT 40
PT 40 + PT 40
Drain Outlet
mm
20
20
20
Temp. range of
Circulation water
Cooling
10°C ~ 45°C(50°F ~ 113°F) 10°C ~ 45°C(50°F ~ 113°F) 10°C ~ 45°C(50°F ~ 113°F)
Heating
-5°C ~ 45°C(23°F ~ 113°F) -5°C ~ 45°C(23°F ~ 113°F) -5°C ~ 45°C(23°F ~ 113°F)