Outside Unit
34
Outside Unit
Refrigerant piping system
➲
Refrigerant pipe diameter from branch to branch (B,C,D)
Downward Indoor Unit
total capacity(kW)
Liquid pipe(mm)
Gas pipe(mm)
≤
5.6
Ø 6.35
Ø 12.7
< 16.0
Ø 9.52
Ø 15.88
≤
23.0
Ø 9.52
Ø 19.05
< 33.0
Ø 9.52
Ø 22.2
< 47.0
Ø 12.7
Ø 28.58
< 71.0
Ø 15.88
Ø 28.58
< 104.0
Ø 19.05
Ø 34.9
< 174.0
Ø 19.05
Ø 41.3
➲
Total pipe length limited
Classification
Section
Type
Y branch
Y/header branch
Header branch
Maximum
permitted
length
Outdoor unit
↔
indoor unit
Maximum pipe
length(L)
A+B+C+D+e
≤
150 m
(Conditionally 200 m)*
A+B+b
≤
150 m
A+C+e
≤
150 m
(Conditionally 200m)*
A+f
≤
150 m
Corresponding
pipe length
175 m
(Conditionally 225 m)*
175 m
(Conditionally 225 m)*
175 m
Total pipe length
(Outdoor unit
↔
total indoor unit)
300 m
(Conditionally 500 m)*
300 m
(Conditionally 500 m)*
300 m
(Conditionally 500 m)*
Permitted
height
Outdoor unit
↔
indoor unit
height
difference(H)
50 m
50 m
50 m
Indoor unit
↔
indoor unit
height
difference(h)
40 m
40 m
40 m
Maximum pipe
length after
1st branch
Actual pipe
length(
l
)
40 m
(Conditionally 90m)*
40 m
(Conditionally 90m)*
40 m
WARNING
• It is recommended that difference of piping length for pipes connected to the Indoor Unit is mini-
mized. Performance difference between Indoor Units may occur.
• When the any one (or both) of below conditions are satisfied, the diameter of main pipe (A) must be
increased according to below table.
- The equivalent length between outdoor unit and the farthest indoor unit is 90m or more
(Liquid and Gas pipes are increased)