Refrigerant piping system
Refrigerant piping system
Y branch method
Slave2
Slave3
Slave1
Master
H
I
G
G
IDU
direction
l
40m (90 m : Conditional application)
L150m (200 m : Conditional application)
h 40 m
10m or
less
ODU Capacity
Master ≥ Slave1 ≥ Slave2 ≥ Slave3
l
40m (90 m : Conditional application)
h 40 m
H 50m
L150m (200 m : Conditional application)
IDU
direction
Series outside unit system
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Header branch
Ⓕ
: Suture
Ⓖ
: Outside branch(1st)
Ⓗ
: Outside branch(2nd)
Ⓘ
: Outside branch(3rd)
Single outside unit system
Example : 5 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Header branch
Ⓕ
: Suture
* If it is conditionally installed, refer to (table 1).
* If it is conditionally installed, refer to (table 1).