Electrical Wiring
◆
The Procedure of Automatic Addressing
• Automatic addressing setting end
Numbers of indoor unit connection set whose addressing is
completed are indicated for 30seconds on 7-segment LED
after completing setting
Indoor address number is displayed on wired remote control or indoor unit
display window. It is not an error message, will disappeared when on/off
button is pressed on remote control
ex) Display of 01, 02, ..., 15 means connection of 15 indoor units and
Automatic addressing is completed normally.
Automatic addressing start
Waiting 3 minutes
Power On
Press RED Button for 5 sec.
(SW01C)
7-segment LED = 88
Don’t press RED Button
(SW01C)
Waiting about 2~7 minutes
7-segment LED
OK
YES
NO
Check the connections
of communication cable
= 88
Turn OFF all DIP switches of the
master main board before
automatic address setting.