Outside Units
20
20
Notes:
1. Voltage range
Voltage supplied to the unit terminals should be within the
minimum and maximum range
2. Maximum allowable voltage unbalance between
phase is 2 %
3. Select wire spec. based on the larger value of MCA or
TOCA.
4. TOCA means the total over current value of each outside
unit.
5. MSC means the Max. current during the starting of
compressor.
6. Recommended circuit breaker is ELCB
(Earth Leakage Circuit Breaker)
7. MFA is used to select the circuit breaker and ground fault
circuit interrupter (earth leakage circuit breaker)
MCA : Minimum Circuit Amperes (A)
MSC : Maximum Starting Current
RLA : Rated Load Amperes (A)
FLA : Full Load Amperes (A)
MFA: Maximum Fuse Amperes(A)
TOCA: Total Over Current Amperes(A)
■
60Hz
Model
Hz
Volts
Voltage-range
COMP
Power Supply
MSC
RLA
MCA
TOCA
MFA
Min.:342
Max.:418
Min.:342
Max.:418
Min.:342
Max.:418
Min.:342
Max.:418
Min.:342
Max.:418
Min.:342
Max.:418
Min.:342
Max.:418
Min.:342
Max.:418
Min.:342
Max.:418
Min.:342
Max.:418
Min.:342
Max.:418
Min.:342
Max.:416
ARWN80LA2
60
380
14.3 20
20
-
13.0
ARWN100LA2
60
380
15.4 20
20
-
14.0
ARWN160LA2
60
380
24.1 38
30
67.0
23.0
ARWN180LA2
60
380
25.2 38
30
67.0
24.0
ARWN200LA2
60
380
27.5 38
30
67.0
25.0
ARWN240LA2
60
380
38.4 58
55
71.0
36.0
ARWN260LA2
60
380
39.5 58
55
71.0
37.0
ARWN280LA2
60
380
41.8 58
55
71.0
38.0
ARWN300LA2
60
380
42.9 58
55
71.0
39.0
ARWN400LA2
60
380
55.0 76
70
82.6
50.0
ARWN500LA2
60
380
70.4 96
90
86.6
64.0
ARWN600LA2
60
380
82.5 114
100
98.2
75.0