Outside Units
15
15
3 phase 4 wires
power supply
60Hz 380V
Power supply
1 Phase 60Hz
220V
Power supply switch
(switch fuse)
3 phase 4 wires power line(R, S, T, N)
Transmission line (3 line): wired remote control
Single phase of power supply line(L, N)
Transmission line (2 shield line): between indoor unit and outside unit
3
4
3
4
3
4
The GND terminal is a '–' terminal for the central controller, not ground line
Outside unit
SODU
B
A
B
A
IDU
INTERNET
DRY1 DRY2 GND
12V
5.2 60Hz
◆
Example Connection of Transmission Cable
■
1 Outside Unit - 3Ø, 380V
WARNING
• Indoor unit ground lines are required for preventing electrical shock accident in current leakage,
transmission disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the
power supply.