OUTDOOR UNITS INFORMATION
9
Power Supply : 1Ø, 220-240 V~, 50 Hz / 1Ø, 220 V~, 60 Hz
CAUTION
• Ratio of the connectable Indoor Units to the Outdoor: Within 50 ~ 160%
• Ratio of running Indoor Units to the Outdoor: Within 10 ~ 100%
• A combination operation over 100% cause to reduce each indoor unit capacity.
!
OUTDOOR UNITS INFORMATION
ENGLISH
System(HP)
2.5
3
4
Model
ARUV025GSR0
ARUV030GSR0
ARUV040GSR0
Refrigerant Precharged
Amount
kg
1
1.4
1.4
lbs
2.2
3.1
3.1
Net weight
kg
45
59
59
lbs
99
130
130
Dimensions (WxHxD)
mm
870x655x320
950x834x330
950x834x330
inch
34.3×25.8×12.6
37.4×32.8×13.0
37.4×32.8×13.0
Piping
Connections
Liquid Pipes
mm(inch)
9.52(3/8)
9.52(3/8)
9.52(3/8)
Gas Pipes
mm(inch)
15.88(5/8)
15.88(5/8)
15.88(5/8)
System(HP)
5
6
Model
ARUV050GSR0
ARUV060GSR0
Refrigerant Precharged
Amount
kg
1.4
1.9
lbs
3.1
5.1
Net weight
kg
66
79
lbs
146
174
Dimensions (WxHxD)
mm
950x834x330
950x1170x330
inch
37.4×32.8×13.0
37.4×46.1×13.0
Piping
Connections
Liquid Pipes
mm(inch)
9.52(3/8)
9.52(3/8)
Gas Pipes
mm(inch)
15.88(5/8)
19.05(3/4)
1,MFL67798026,영영 19. 3. 14. 영영 4:48 Page 9