62
ELECTRICAL WIRING
ENGLISH
Main power OFF
PCB DIP swich No. 5, No. 6 ON
Main power ON
Display low pressure on 7-segment
Change low preesure
(UE, U4 : TACT-SW01
U5 : TACT-SW02)
Select low preesure
(UE, U4 : TACT-SW02
U5 : TACT-SW01)
PCB DIP swich No. 5, No. 6 OFF
Main power OFF
Target pressure adjusting
Mode setting method
CAUTION
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
!
Setting
No.
low pressure
(kPa)
1
699
2
739
3
778
4
843
5
895
6
908