PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
33
ENGLISH
Header Method
Example : 6 Indoor Units connected
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch
Ⓒ
: Indoor Units
Ⓓ
: Sealed piping
L 150m
H 50m
40m
• * : Assume equivalent piping length of Y branch to be 0.5m, that of header to be 1m, calcu-
lation purpose
• Indoor Unit should be installed at lower position than the header.
WARNING
Pipe length after header branching (a~f)
It is recommended that difference in length of the pipes connected to the Indoor Units is
minimized. Performance difference between Indoor Units may occur.
!
Outdoor unit capacity (HP)
2.5
3
4
5
6
T
Total pipe length (m)
50
80
85
100
100
A+B+C+a+b+c+d+e
L
Longest pipe length (m) (Equivalent pipe length)
30
40
50
50
50
A+B+C+D+e
l
Longest pipe length after 1st branch (m)
20
30
30
30
30
B+C+D+e
H
Difference in height (m) (Outdoor Unit
÷
Indoor Unit)
15
15
15
15
15
H
h
Difference in height (m) (Indoor Unit
÷
Indoor Unit)
7.5
7.5
7.5
7.5
7.5
h