ELECTRICAL WIRING
ENGLISH
Field Wiring
(Main Switch)
Power supply
(1-phase 2-wire)
Power supply Swich
Power cable (2-wire Cable)
Communication cable(3-wire Cable)
Communication cable (2-wire Cable)
Pull Box
L
N
G
1.5mm
2
ƣ
,
1.5mm
2
ƣ
,
1.5mm
2
ƣ
,
3
4
3
4
3
4
Outdoor Unit
SODU B SODU A IDU B
IDU A
INT B
INT A
Between Indoor and Outdoor unit
The GND terminal at the main PCB is a ‘-’ ter-
minal for day contact, it is not the point to
make ground connection.
WARNING
• Indoor Unit ground wires are required for preventing electrical shock accident during current
leakage, Communication disorder by noise effect and motor current leakage (without connec-
tion to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately
from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because
this system consists of the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power
goes on and off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
!
Frequency
Voltage range(V)
Outdoor
Indoor
60Hz
220V
220V
50Hz
220~240V 220~240V