26
ENGLISH
NOTE
!
Use the Valve Group Control when 2 branches are connected with only 1 indoor
unit which has higher capacity than 61 kBTU.
NOTE
!
If the large capacity indoor units are installed, below Y branch pipe should be
used.
Models
ARBLB03321
Low Pressure
Gas Pipe
High Pressure
Gas Pipe
Liquid pipe
413
390
I.D19.05
I.D19.05
I.D19.05
I.D12.7
I.D12.7
70
I.D15.88
I.D15.88
I.D25.4
I.D25.4
O.D25.4
80
110
83
1
2
3
3
O.D19.05
O.D19.05
1
2
I.D22.2
I.D22.2
I.D22.2
I.D28.58
I.D12.7
I.D12.7
I.D12.7
74
332
321
I.D6.35
I.D6.35
I.D9.52(3/8)
I.D9.52
I.D9.52
I.D15.88
I.D12.7
I.D12.7
70
I.D25.4
110
I.D19.05
I.D19.05
2
3
2
3
O.D15.88
444
421
96
I.D15.88
I.D22.2
I.D22.2
I.D22.2
O.D15.88
I.D19.05
I.D9.52
Slave
Slave
1) Selection of the method for pipe detection of an HR unit
(Auto/Manual)
Auto
Manual
Master
Master
Switch No.1 Off
Switch No.1 On
2) Selection of Master/Slave Main PCB
Master
Slave
Switch No.5 Off
Switch No.5 On
* Master Only
NOTE
!
Do not turn on any SW02E on Slave Main PCB except No.5.
3) Setting the zoning control
SW02E setting
SW01E setting
Normal
control
Master
SW01E
Zoning
control
Master
Master
SW01E
Turn the dip switch of
the zoning branch on.
EX) Branch 1,2 are
zoning control.
4) Selection of the No. of connected branches
1 branch
Connected
5 branch
Connected
2 branches
Connected
6 branch
Connected
3 branches
Connected
7 branch
Connected
4 branches
Connected
8 branch
Connected
* Master Only
* Master Only
* Master Only
h
Each model is shipped with the switches No.2, 3, 4 pre-adjusted as
above in the factory.
WARNING
If you want to use a “Model” for “No. of using branch(es)” HR
Unit after closing the “Closing pipe No.”, set the dip switch for
“No. of using branch(es)” HR Unit.
Ex) If you want to use a PRHR083 for 4 branches HR Unit after
closing the 5~8th pipes, set the dip switch for 4 branches HR
Unit.
!
Main function of SW01D
1) Selection of the Valve Group Control
h
Y branch pipe
[Unit : mm(inch)]
Valve Group
SW01D
Setting
Valve Group
SW01D
Setting
Not control
0
No. 5,6/7,8 Valve Control
8
No. 1,2 Valve Control
1
No. 1,2/5,6 Valve Control
9
No. 2,3 Valve Control
2
No. 1,2/7,8 Valve Control
A
No. 3,4 Valve Control
3
No. 3,4/5,6 Valve Control
B
No. 5,6 Valve Control
4
No. 3,4/7,8 Valve Control
C
No. 6,7 Valve Control
5
No. 1,2/3,4/5,6 Valve Control
D
No. 7,8 Valve Control
6
No. 1,2/3,4/6,7 Valve Control
E
No. 1,2/3,4 Valve Control
7
No. 1,2/3,4/7,8 Valve Control
F
* Master Only
SW01C (Rotary S/W for addressing HR unit)
Must be set to '0' when installing only one HR unit.
When installing multiple HR units, address the HR units with sequen-
tially increasing numbers starting from '0'.
Maximum 16 HR Units can be installed.
Ex) Installation of 3 HR units
SW01B/SW01C/SW01E/SW02B
(Dip S/W and push S/W for Manual pipe detection)
- Set the address of the valve of the HR unit to the central control ad-
dress of the connected indoor unit.
- SW01E: selection of the valve to address
SW02B: increase in the digit of 10 of valve address
SW01B: increase in the last digit of valve address
SW01C: Manual addressing of zoning indoor units (use for Zoning
setting)
- Prerequisite for Manual pipe detection : central control address of
each indoor unit must be preset differently at its wired remote con-
trol.
A B
A B
A B
* Master Only