background image

29

ENGLISH

Identification of Manual Valve ID (Address)

No.

Display and setup

Setup and Contents

1

7-SEG

SW01E

- Operation: more than 2 dip switches

turned on. 

- Display: "Er" is displayed in 7-SEG

7) The rotary switch set value of above number of indoor units which is

connected with FF and prevents a malfunction. 
(Example: The case where  3 indoor units is connected in piping 1,
sets from rotary switch 0,1,2 and 3,4,5,6,7 with FF set) 

- Prerequisite for manual valve addressing: central control address of

each indoor unit must be preset differently at its wired remote con-
trol.

- Above setup must be done for all HR unit valves.

- The valve that is not connected with any indoor unit should be ad-

dressed with any other number than used address numbers of the
valves connected with indoor units.(The valves does not work if the
address numbers are same.) 

No.

Display and setup

Setup and Contents

1

7-SEG

SW01E

SW02B

SW01B

0

SW01C

- Operation: None

- Display: None 

2

7-SEG

SW01E

SW02B

SW01B

SW01C

0

- Operation : Turn dip S/W No.1 on to ad-

dress valve #1

- Display : Existing value saved in EEP-

ROM is displayed in 7-SEG.

3

7-SEG

SW01E

SW02B

SW01B

SW01C

0

- Operation : Set the digit of 10(1) to the

number in Group High data of the wired
remote control connected to the corre-
sponding indoor unit to the valve #1 by
pressing left tack S/W.

- Display : Digit increasing with the times

of pressing tack S/W is displayed in left
7-SEG.

4

1

7-SEG

SW01E

SW02B

SW01B

SW01C

- Operation : SW01C : 1

- Display : Display former value.

5

7-SEG

SW01E

SW02B

SW01B

SW01C

1

- Operation : Setting No. using SW02B 

and SW01B, SW01C : 1

- Display : Display setting value.

6

7-SEG

SW01E

SW02B

SW01B

SW01C

1

- Operation : Turn dip S/W No.1 off to save

the address of valve #1

- Display : "11" displayed in 7-SEG disap-

pears.

7

7-SEG

SW01E

SW02B

SW01B

SW01C

0

- Operation : Return valve of addressing

HR unit.

- Display : None

Setting the function 

Select the mode/function/option/value using ‘

’, ‘

’ Button and con-

firm that using the ‘

’ button after dip switch No.5 is turned on.

DIP-SWITCH

SW01D(reset)

SW04C(x:cancel)

7-Segment 

SW03C(

:forward)

SW02C(

:backward)

SW01C(●:confirm)

Method of checking the pipe detection result
at HR unit

In case that an indoor unit of central control address "11" is connected to a
valve #1 of an HR unit

No.

Display and setup

Setup and Contents

1

7-SEG

SW01E

- Operation: Turn dip S/W No.1 on. 

- Display: "11" is displayed in 7-SEG

2

7-SEG

SW01E

- Operation: Turn dip S/W No.1 off. 

- 7-SEG disappeared 

1,MFL69717904,영영  18. 8. 29.  영영 2:50  Page 29

Summary of Contents for MULTI V S ARUB060GSS4

Page 1: ...accordance with the national wiring standards by authorized personnel only Please retain this installation manual for future reference after reading it thoroughly Original instruction Copyright 2018 LG Electronics Inc All Rights Reserved ENGLISH ITALIANO ESPAÑOL FRANÇAIS DEUTSCH ČEŠTINA ΕΛΛΗΝΙΚΆ NEDERLANDS POLSKI LIMBA ROMÂNĂ РУССКИЙ ЯЗЫК УКРАÏНСЬКА 1 MFL69717904 영영 18 8 29 영영 2 49 Page 1 ...

Page 2: ...s can result in hazards to you and oth ers The information contained in the manual is intended for use by a qualified service tech nician familiar with safety procedures and equipped with the proper tools and test in struments Failure to carefully read and follow all in structions in this manual can result in equip ment malfunction property damage personal injury and or death Installation Have all...

Page 3: ... could not enter the prod uct There is risk of fire electric shock or product damage Do not touch the power switch with wet hands There is risk of fire electric shock explosion or injury When the product is soaked flooded or sub merged contact an Authorized Service Center There is risk of fire or electric shock Be cautious not to touch the sharp edges when installing It may cause injury Take care ...

Page 4: ...s of transportation It is dangerous Do not touch the heat exchanger fins Doing so may cut your fingers When transporting the outdoor unit suspending it at the specified positions on the unit base Also support the outdoor unit at four points so that it cannot slip sideways Safely dispose of the packing materials Packing materials such as nails and other metal or wooden parts may cause stabs or othe...

Page 5: ...uum drying 21 Vacuum Mode 21 Thermal insulation of refrigerant piping 22 ELECTRICAL WIRING 22 Caution 23 Control box and connecting position of wiring 23 Communication and Power Cables 24 Wiring of main power supply and equipment capacity 24 Field Wiring 25 Checking the setting of outdoor units 25 HR UNIT PCB 25 Setup the switch of HR Unit 27 Automatic Addressing 28 Example of manual valve address...

Page 6: ... hours CAUTION The above list indicates the order in which the individual work opera tions are normally carried out but this order may be varied where local conditions warrants such change The thickness of the piping should comply with the relevant local and national regulations for the designed pressure 3 8MPa 551 1psi Since R410A is a mixed refrigerant the required additional refrigerant must be...

Page 7: ...r on a high story of a building secure a normal fan operation by using a duct or a wind shield Install the unit so that its discharge port faces to the wall of the build ing Keep a distance 500mm 19 11 16inch or more between the unit and the wall surface Supposing the wind direction during the operation season of the air conditioner install the unit so that the discharge port is set at right angle...

Page 8: ...r more 500 19 5 8 or less 1000 39 1 4 or more 100 3 15 16 ormore 100 3 15 16 ormore 1000 39 1 4 or more 300 11 13 16 or more INSTALLATION SPACE Unit mm inch Unit mm inch In case of obstacles on the discharge side 1 Stand alone installation 500 19 5 8 or more 500 19 5 8 or less 1000 39 1 4 or more 500 19 5 8 or more 1000 39 1 4 or more 100 3 15 16 or more 500 19 5 8 or less 1000 39 1 4 or more 1000...

Page 9: ...l the outdoor unit 500mm higher than the average snowfall Remove any snow that piles higher than 100mm on the top of the unit In areas of high wind do not install the units heat exchanger or dis charge fan perpendicular to the wind direction Air guide work In cases where the outdoor unit is installed in an enclosed space care should be taken to ensure adequate airflow around the product other wise...

Page 10: ...boards in the locations where the casing comes in contact with the sling to prevent damage Hoist the unit making sure it is being lifted at its center of gravity Fix the unit tightly with bolts as shown below so that unit will not fall down due to earthquake or gust Use the H beam support as a base support Noise and vibration may occur from the floor or wall since vibration is transferred through ...

Page 11: ...of the 2 fixation holes on the rear side of the unit C wires Flaring work Carry out flaring work using flaring tool as shown below Firmly hold copper tube in a bar or die as indicated dimension in the table above Check Compare the flared work with figure below If flare is noted to be defective cut off the flared section and do flar ing work again Burrs removal Completely remove all burrs from the ...

Page 12: ... 1 Ø19 05 3 4 14 0 1 4 10 3 1 0 110 10 81 1 7 4 Ø22 2 7 8 30 0 3 0 22 1 2 2 8mm 0 31inch 25 3 0 18 5 2 2 Ø25 4 1 0 Regulator Auxiliary valve Taping Should not contain air Welding Point Note should not block the outlet side When the internal pressure in pipe is abo ve the atmospheric pressure pinhole is o ccurred and it is a leakage cause Oxide scale Nitrogen Nitrogen gas Pressure 0 02MPa 2 9psi le...

Page 13: ...in the figure Installation of Outdoor Unit HR Unit and In door Unit Refrigerant Pipe 3 pipes are connected to the HR unit from the outdoor unit classified into liquid pipe low pressure gas pipe and high pressure gas pipe de pending on status of refrigerant passing through the pipe You must connect 3 pipes from outdoor unit to HR unit For connection between indoor unit and HR unit you must connect ...

Page 14: ...unit reducer PRHR023 A OD22 2 7 8 Ø19 05 3 4 Ø15 88 5 8 OD15 88 5 8 Ø12 7 1 2 Ø6 35 1 4 OD9 52 3 8 OD19 05 3 4 Ø15 88 5 8 OD12 7 1 2 Ø9 52 3 8 Ø12 7 1 2 OD22 2 7 8 Ø19 05 3 4 Ø15 88 5 8 OD15 88 5 8 Ø12 7 1 2 PRHR033 A PRHR043 A PRHR063 A PRHR083 A OD19 05 3 4 Ø15 88 5 8 OD28 58 1 1 8 Ø22 2 7 8 Ø19 05 3 4 OD15 88 5 8 Ø12 7 1 2 Ø6 35 1 4 OD9 52 3 8 OD12 7 1 2 Ø9 52 3 8 OD15 88 5 8 Ø12 7 1 2 Ø9 52 3 ...

Page 15: ...e the leakage prevention cap attached to the outdoor unit service valve before pipe work Proceed the leakage prevention cap removal as follows Verify whether the liquid gas pipes are locked Extract remaining refrigerant or air inside using the service port Remove the leakage prevention cap Service Port Refrigerant Charging Port Liquid pipe High Pressure gas pipe Leakage prevention cap Low Pressure...

Page 16: ... height Indoor Unit Indoor Unit h 15m 49ft a b Difference in height HR unit HR unit a 15m 49ft b 5m 16ft Upward outdoor unit total capacity Pipe diameter Pipe diameter when pipe length is 90m 295 ft HP Liquid mm inch Low pres sure gas pipe mm inch High pres sure gas pipe mm inch Liquid mm inch Low pres sure gas pipe mm inch High pres sure gas pipe mm inch 6 Ø9 52 3 8 Ø19 05 3 4 Ø15 88 5 8 Ø 12 7 1...

Page 17: ...A 1 2 3 4 5 14 5kW 48kBtu h 7 25kW 24kBtu h 7 25kW 24kBtu h 3 63kW 12kBtu h 3 63kW 12kBtu h 7 25kW 24kBtu h 14 5kW 48kBtu h 14 5kW 48kBtu h 14 5kW 48kBtu h Pattern 7 Pattern 8 HR1 A A A 1 2 Serial connection of HR units Capacity sum of indoor units 192 kBtu h Maximum indoor units per a branch are 8 indoor units HR2 3 4 HR3 5 6 HR1 1 2 HR2 B 3 4 5 6 7 8 14 5kW 48kBtu h 14 5kW 48kBtu h 14 5kW 48kBtu...

Page 18: ... m 0 179 lbs ft Total liquid pipe Ø15 88 mm 5 8 inch x 0 173 kg m 0 116 lbs ft Total liquid pipe Ø12 7 mm 1 2inch x 0 118 kg m 0 079 lbs ft Total liquid pipe Ø9 52 mm 3 8inch x 0 061 kg m 0 041 lbs ft Total liquid pipe Ø6 35 mm 1 4 inch x 0 022 kg m 0 015 lbs ft Number of installed HR unit x 0 5 kg 1 1 lbs CF value of indoor unit WARNING Regulation for refrigerant leakage the amount of refrigerant...

Page 19: ...8 70 2 3 4 O D19 05 3 4 I D22 2 7 8 O D25 4 1 I D28 58 1 1 8 80 3 5 32 I D25 4 1 110 4 11 32 O D19 05 3 4 I D22 2 7 8 413 16 1 4 390 15 11 32 I D12 7 1 2 I D12 7 1 2 I D12 7 1 2 74 2 29 32 332 13 1 16 321 12 5 8 I D6 35 1 4 I D6 35 1 4 I D9 52 3 8 I D9 52 3 8 I D9 52 3 8 ARBLN 07121 2 3 1 2 1 3 I D12 7 1 2 376 14 13 16 404 15 29 32 120 4 23 32 120 4 23 32 90 3 17 32 I D15 88 5 8 I D15 88 5 8 I D19...

Page 20: ...010 ID9 52 3 8 ID6 35 1 4 ID9 52 3 8 ID6 35 1 4 ID9 52 3 8 ID6 35 1 4 ID15 88 5 8 ID12 7 1 2 150 5 29 32 120 4 23 32 ID15 88 5 8 ID15 88 5 8 ID12 7 1 2 ID19 05 3 4 ID22 2 7 8 ID28 58 1 1 8 ID25 4 1 775 30 17 32 182 7 5 32 ID9 52 3 8 ID6 35 1 4 ID9 52 3 8 ID6 35 1 4 150 5 29 32 120 4 23 32 ID9 52 3 8 ID9 52 3 8 ID6 35 1 4 ID6 35 1 4 ID9 52 3 8 ID6 35 1 4 ID9 52 3 8 ID9 52 3 8 ID12 7 1 2 ID6 35 1 4 ...

Page 21: ...ion lines Separation Power lines E D D B A C Thermal insulation of refrigerant piping NOTE Always add an appropriate amount of refrigerant For the refrigerant addi tional charge Too much or too little refrigerant will cause trouble To use the Vacuum Mode If the Vacuum mode is set all valves of Indoor units and Outdoor units will be opened WARNING Use a vacuum pump or Inert nitrogen gas when doing ...

Page 22: ... accordance with regulations and this installation manual If power supply circuit has a lack of capacity or electric work defi ciency it may cause an electric shock or fire Caution Follow ordinance of your governmental organization for technical standard related to electrical equipment wiring regulations and guid ance of each electric power company ELECTRICAL WIRING Penetrations 2 Core Shield Cabl...

Page 23: ...ection 1 0 1 5mm2 1 55x10 3 2 32x10 3 in2 Maximum allowable temperature 140 F Maximum allowable cable length under 1 000m 3 281ft Remote control cable Types 3 core cable Central control cable Separation of communication and power cables If communication and power cables are run alongside each other then there is a strong likelihood of operational faults developing due to in terference in the signa...

Page 24: ...er Option Single phase of power supply line L1 L L2 N Communication line 3 line Wired remote control Communication line 2 shield line Between Indoor Unit and Outdoor Unit Power supply 1 Phase 220 240V 50Hz 220V 60Hz Power supply 1 Phase 220 240V 50Hz 220V 60Hz HR unit HR unit WARNING Indoor Unit ground wires are required for preventing electrical shock ac cident during current leakage Communicatio...

Page 25: ...ain PCB 2EA same P No 7 SEG Liquid Bypass Valve SW02E Use only SW No 5 SW01E Branch 5 8 from SW No 1 SW01C SW01D SW01C SW02B SW01B SW02E SW01E Branch 1 4 from SW No 1 Branch No Main PCB Master Main PCB Slave Number from left in sequence for less than 8 branch model PRHR043 PRHR033 PRHR023 Master Only Main function of SW02E Setup the switch of HR Unit ON S W Selection No 1 Method for pipe detection...

Page 26: ...tory WARNING If you want to use a Model for No of using branch es HR Unit after closing the Closing pipe No set the dip switch for No of using branch es HR Unit Ex If you want to use a PRHR083 for 4 branches HR Unit after closing the 5 8th pipes set the dip switch for 4 branches HR Unit Main function of SW01D 1 Selection of the Valve Group Control h Y branch pipe Unit mm inch Valve Group SW01D Set...

Page 27: ...fter completing addressing address of each indoor unit is indicated on the wired remote control display window CH01 CH02 CH03 CH06 Indicated as numbers of connected indoor units Heat Recovery SERVICE PCB S W No Setup No 1 Manual addressing of valve 1 Master 5 Slave No 2 Manual addressing of valve 2 Master 6 Slave No 3 Manual addressing of valve 3 Master 7 Slave No 4 Manual addressing of valve 4 Ma...

Page 28: ...2E of HR unit PCB on NO YES Example of manual valve addressing Non Zoning setting In case that an indoor unit of central control address 11 is connected to a valve 1 of an HR unit Prerequisite for manual valve addressing central control address of each indoor unit must be preset differently at its wired remote con trol Above setup must be done for all HR unit valves The valve that is not connected...

Page 29: ...01C 0 Operation Set the digit of 10 1 to the number in Group High data of the wired remote control connected to the corre sponding indoor unit to the valve 1 by pressing left tack S W Display Digit increasing with the times of pressing tack S W is displayed in left 7 SEG 4 1 7 SEG SW01E SW02B SW01B SW01C Operation SW01C 1 Display Display former value 5 7 SEG SW01E SW02B SW01B SW01C 1 Operation Set...

Page 30: ...t WARNING Valve address and central control address of its corresponding indoor unit should be set identical in manual addressing TEST RUN Cool Heat selector Mode setting method Service PCB DIP switch on No 5 Select the mode using Button Func Push the button Select the Function using Button Fn1 Push the button Select the Option using Button oFF op1 op2 Push the button Cool Heat Selection mode is s...

Page 31: ...8 6 5 10 5 op9 5 12 op10 continuous operation op11 continuous operation op12 continuous operation op13 6 5 10 5 op14 6 5 10 5 op15 6 5 10 5 Service PCB DIP switch on No 5 Select the mode using Button Func Push the button Select the Function using Button Fn5 Push the button Select the Option using Button 0 255 Push the button ODU address is set CAUTION Ask an authorized technician to setting a func...

Page 32: ...elect the Option using Button HEAT COOL Push the button CAUTION Ask an authorized technician to setting a function If do not use a function set an off mode Change a power consumption or capacity Setting Target pressure adjusting Mode setting method Mode Low Pressure kpa High pressure kpa oFF 804 2990 op1 699 3121 op2 739 2827 op3 843 2696 op4 908 2565 op5 961 2435 op6 1026 2304 op7 804 2990 1 MFL6...

Page 33: ...f by Outdoor Unit high pressure switch 2 5 Outdoor Unit Input Voltage High Low Voltage Outdoor Unit input voltage is over 289V or below 73V ARUB BTE4 Outdoor Unit input voltage is over 506V or below 414V ARUB DTE4 2 6 Outdoor Unit Inverter Compressor Start Failure The First Start Failure by Outdoor Unit Inverter Compressor Abnor mality 2 9 Outdoor Unit Inverter Compressor Over Current Outdoor Unit...

Page 34: ...1 6 Outdoor Unit Oil Level Sensor Error Oil Level Sensor of Outdoor Unit is open or short 1 4 5 outdoor unit Main Board External Board communica tion Error outdoor unit Main Board External Board communication Error 1 5 1 Failure of operation mode conversion at Outdoor Unit Failure of operation mode conversion at Outdoor Unit 1 5 3 Outdoor Unit Heat Exchanger Temperature Sensor upper part Fault Out...

Page 35: ...of smallest room whereindoor unit is installed m3 ft3 In case the result of calculation exceeds the limiting concentration perform the same calculations by shifting to the second smallest and the third small est rooms until at last the result is below the limiting concentration Refrigerant concentration Kg m3 lbs ft3 R410A In case the concentration exceeds the limit When the concentration exceeds ...

Page 36: ...er to the bar code on the product Product Sales Name Model Factory Name ARUx ySSz x N Heat Pump V Cooling only B Heat Recovery y G 1Ø 220 240V 50Hz z Numeric Series Number Numeric Cooling capacity Product information Airborne Noise Emission The A weighted sound pressure emitted by this product is below 70 dB The noise level can vary depending on the site The figures quoted are emission level and a...

Page 37: ...ve LG Electronics European Shared Service Center B V Krijgsman 1 1186 DM Amstelveen The Netherlands Manufacturer LG Electronics Inc Changwon 2nd factory 84 Wanam ro Seongsan gu Changwon si Gyeongsangnam do KOREA 1 MFL69717904 영영 18 8 29 영영 2 49 Page 80 ...

Reviews: