Installation Manual
33
Refrigerant piping installation
3 Outdoor Units
10m or
less
Example : 5 Indoor Units
connected
: Outdoor Unit
: 1st branch (Y branch)
: Indoor Units
: Downward Indoor Unit
: Connection branch pipe
between Outdoor units:
ARBL302C
: Connection branch pipe
between Outdoor units:
ARBL202C
➲
Sub2 Outdoor unit ~ Connection branch pipe
Pipe diameter (F)
High/Low Pressure Common pipe
(mm)
Ø19.05(3/4 inch)
Ø12.7(1/2 inch)
Ø28.58(1
1
/
8
inch)
Liquid pipe
(mm)
Gas pipe
(mm)
High/Low Pressure Common pipe
(mm)
Ø19.05(3/4 inch)
Ø19.05(3/4 inch)
Ø38.1(1
1
/
2
inch)
Liquid pipe
(mm)
Gas pipe
(mm)
➲
Connection branch pipe
~ Connection branch pipe
Pipe diameter (E)
➲
Connection branch pipe
~ Main pipe diameter (A)
Ø22.2(7/8 inch)
Ø44.5(1
3
/
4
inch)
Liquid pipe
(mm)
Gas pipe
(mm)
WARNING
• Main pipe must be always come out to direction of the Main Outdoor Unit in installation.
• For installing the refrigerant pipe system between Outdoor Units, use the connection branch pipe
between Outdoor Units.