28
Outdoor Unit
Ø 28.58
Ø 38.1
❈
Branch Pipe for Connection between Outdoor Units: ARBL202C
❈
Branch Pipe for Connection between Outdoor Units: ARBL302C
❈
Branch Pipe for Connection between Outdoor Units: ARBL202C
❈
Branch Pipe for Connection between Outdoor Units: ARBL302C
Main Pipe
Main Pipe
Sub2 + Sub1 Outdoor
Unit Connection Pipe
Sub1 Outdoor Unit
Main Outdoor Unit
Ø 12.7
Ø 12.7
Ø 12.7
Sub1 + Main Outdoor
Unit Connection Pipe
After cutting to length
(Don't cut the pipe of
less than 70mm)
Sub2 + Sub1 Outdoor
Unit Connection Pipe
Sub1 Outdoor Unit
Gas Pipe
Sub1 Outdoor
Unit Gas Pipe
Weld elbow while
flowing nitrogen.
After cutting to length
(Don't cut the pipe of
less than 70mm)
Sub1 + Main Outdoor
Unit Connection Pipe
Main Outdoor Unit
Gas Pipe
Main Outdoor
Unit Gas Pipe
Weld elbow while
flowing nitrogen.
Ø 44.5
Ø 19.05
Ø 22.2
Ø 19.05
Ø 28.58
Ø 38.1
Ø 28.58
Y branch
A
B
To outdoor unit
To branch piping or indoor unit
A
B
Facing
upwards
Facing
downwards
Within
±
3
°
Within
±
3
°
Viewed from point A
in direction of arrow
/- 10
°
Refrigerant piping installation
2 Outdoor Units
3 Outdoor Units
CAUTION
Both the High/Low Pressure Common pipe and the Liquid pipe shall be insulated by insulation material.
After cutting to length
(Don't cut the pipe of less
than 70mm)
❈
Branch Pipe for Connection between Outdoor Units: ARBL202C
Sub Outdoor
Gas Pipe
Main Outdoor
Gas Pipe
Weld elbow while
flowing nitrogen.
Ø 28.58
Ø 38.1
Ø 28.58
Sub Outdoor
Liquid pipe
Main Outdoor
Liquid Pipe
Main Pipe
Main Pipe
Ø 12.7
Ø 12.7
Ø 19.05
Connection of Gas pipe
Connection of Liquid pipe
Connection of Liquid(Gas) pipe
Connection of Gas pipe
Connection of Liquid pipe