Installation Manual
51
Pipe connections between indoor and outdoor unit
This function is used for creating vacuum in the system after compressor replacement, ODU parts
replacement or IDU addition/replacement.
Master unit PCB DIP switch on
- Heat pump : switch on 11,14
- Cooling only : switch on 10,12,13
Vacuum mode setting
ODU V/V OPEN
Main EEV, SC EEV OPEN
IDU EEV OPEN
ODU power reset
Press the black button Main PCB (5 sec.)
Vacuum mode setting method
Master unit PCB DIP switch off
- Heat pump : switch off 11,14
- Cooling only : switch off 10,12,13
Power reset
Vacuum mode cancellation
CAUTION
ODU operation stops during vacuum mode. Compressor can't operate.
E
N
G
L
IS
H
Vacuum mode cancellation method
Vacuum Mode