34
Outdoor Unit
Pipe connections between indoor and outdoor unit
Longest pipe length * Equivalent pipe length
A+f
≤
200m A+f
≤
225m
Longest pipe length after 1st branch
f
≤
40m
Difference in height(Outdoor Unit
1
Indoor Unit)
H
≤
110m
Difference in height (Indoor Unit
1
Indoor Unit)
h
≤
15m
Difference in height (Outdoor Unit
1
Outdoor Unit)
h1
≤
5m
L
l
H
h
h1
ò
Total pipe length = A+a+b+c+d+e+f
≤
1,000m
WARNING
Pipe length after header branching
(a~f)
It is recommended that difference in
length of the pipes connected to the
Indoor Units is minimized.
Performance difference between
Indoor Units may occur.
• * :
Assume equivalent piping length of Y branch to be 0.5m, that of header to be 1m, calculation purpose
• Indoor Unit should be installed at lower position than the header.
• Piping length from outdoor branch to outdoor unit
≤
10m, equivalent length : max 13m
(for 22HP or more)
Branch pipe can not be used after header
Branch pipe can not be used after header
3 Outdoor Units
Example : 6 Indoor Units connected
?
: Outdoor Unit
?
: Header branch
: Indoor Units
: Sealing
?
: Connection branch pipe
between Outdoor units:
ARCNN31
?
: Connection branch pipe
between Outdoor units:
ARCNN21
10m or
less
H
1
1
0
m
L 200m
40m
Master
Slave2
Slave1
ODU Capacity
Master
≥
Slave1
≥
Slave2
4 Outdoor Units
Example : 6 Indoor Units connected
?
: Outdoor Unit
?
: Header branch
: Indoor Units
: Sealing
?
: Connection branch pipe
between Outdoor units:
ARCNN41
?
: Connection branch pipe
between Outdoor units:
ARCNN31
: Connection branch pipe
between Outdoor units :
ARCNN21
10m or
less
H
1
1
0
m
L 200m
40m
Master
Slave3
Slave1
Slave2
G
F
E
G
F
E
ODU Capacity
Master
≥
Slave1
≥
Slave2
≥
Slave3
D
C
D
C
G