System Tag or ID___________________________________
Job Name_______________________________________
Project Manager__________________________________
Date___________________________________________
Line #
Description
Chassis I.D.
Size
Quantity
CF (Ref.)
1
Total (lbs.)
1
Linear feet of 1/4" liquid line tubing
2
—
—
0.015
2
Linear feet of 3/8" liquid line tubing
2
—
—
0.041
3
Linear feet of 1/2" liquid line tubing
2
—
—
0.079
4
Linear feet of 5/8" liquid line tubing
2
—
—
0.116
5
Linear feet of 3/4" liquid line tubing
2
—
—
0.179
6
Linear feet of 7/8" liquid line tubing
2
—
—
0.238
7
Linear feet of 1" liquid line tubing
2
—
—
0.323
8
Wall M Art Cool Mirror
SE
7k to 15k
0.53
9
Wall M Art Cool Mirror
S8, S5
18k to 24k
0.62
10
1-Way Cassette
TJ
7k to 12k
0.44
11
2-Way Cassette
TL
18k to 24k
0.35
12
4-Way 2' x 2' Cassette
TR
5k to 7k
0.40
13
4-Way 2' x 2' Cassette
TR
9k to 12k
0.55
14
4-Way 2' x 2' Cassette
TQ
15k to 18k
0.71
15
4-Way 3' x 3' Cassette
TN
9k to 15k
1.06
16
4-Way 3' x 3' Cassette
TM
18k to 24k
1.41
17
4-Way 3' x 3' Cassette
TP
24k to 28k
1.06
18
4-Way 3' x 3' Cassette
TN
36k
1.41
19
4-Way 3' x 3' Cassette
TM
42k to 48k
1.41
20
High Static Ducted
BH
7k to 24k
0.57
21
High Static Ducted
BG
15k to 42k
0.97
22
High Static Ducted
BR
48k to 54k
1.37
23
High Static Ducted
B8
76k to 95k
2.20
24
Low Static Ducted, Low Static Ducted Bottom Return
B1, B3
7k to 15k
0.37
25
Low Static Ducted, Low Static Ducted Bottom Return
B2, B4
18k to 24k
0.82
26
Vertical / Horizontal Air Handling Unit
NJ
12k to 24k
1.04
27
Vertical / Horizontal Air Handling Unit
NJ
30k
1.04
28
Vertical / Horizontal Air Handling Unit
NJ
36k
1.57
29
Vertical / Horizontal Air Handling Unit
NK
42k to 54k
2.00
30
Ceiling Suspended
VJ
18k to 24k
0.77
31
Convertible Surface Mount—Ceiling/Wall
VE
9k to 12k
0.22
32
Floor Standing
CE (U)
7k to 15k
0.37
33
Floor Standing
CF (U)
18k to 24k
0.82
34
Additional Refrigerant Charge Required
35
Space II Unit Factory Refrigerant Charge
ARUN053GF2
53K
7.7
36
Total System Charge: Sum of Additional Refrigerant Charge Required and Space II Unit Factory Refrigerant Charge
System Refrigerant Charge Calculator (lbs.).
1
CF (Ref.) = Correction Factor for Refrigerant Charge.
2
For refrigerant charge purposes, consider only the liquid line; ignore the vapor line(s).
The system will stop operation due to excessive or insufficient refrigerant, therefore, always charge the unit properly. When servicing, always
refer to any notes about system piping length and additional refrigerant amounts.
refrIGerant cHarGe WorKsHeet