53
Electrical W
iring
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Figure 60: Indoor Unit Auto Addressing Procedure Flowchart.
Auto addressing procedure is complete. The number of indoor
units that have successfully completed the auto addressing
procedure will display on the LED for thirty (30) seconds.
Address number of each indoor unit is shown on the wired remote controller
display or on the indoor unit display. The address number will disappear
after pressing the on / off button on the remote controller. If CH01, CH02...
CH06 is displayed, that means that six (6) indoor units have been successfully
auto addressed.
Initiate auto addressing procedure.
Wait three (3) minutes.
Power On.
Press/hold Auto Address Button
SW02V for five (5) seconds.
LED displays = 88
Wait three (3) to seven (7) minutes.
LED displays
Auto addressing successful.
YES
NO
Check the communication
cable connections.
= 88
Space Unit sequences through
self diagnostics check. Wait until
LED is blank.
electrIcal WIrInG
Auto Addressing the Indoor Units