1. The above table shows the correlation between the air rates and E.S.P.
2. E.S.P. is given after subtracting coil losses motor step factory installed
3. E.S.P. can be higher than the maximum given in the table, but the unit faces the problem of freezing the coil.
ARNUPBSGB30(Accessory), PBSC30(Accessory)
ARNUPBSGB30(Accessory), PBSC30(Accessory)
ARNUPBSGB30(Accessory), PBSC30(Accessory)
ARNUPBSGB30(Accessory), PBSC30(Accessory)
ARNUPBSGB40(Accessory), PBSC40(Accessory)
ARNUPBSGB40(Accessory), PBSC40(Accessory)
Static Pressure(mmAq (in.Aq))
Setting Value
0(0)
1(3.93)
2(7.87)
3(0.11)
4(0.15)
60
6.29(222)
3.03(107)
0.93(32)
-
-
65
6.61(233)
4.84(170)
1.52(53)
-
-
70
7.69(271)
5.64(199)
2.18(76)
0.79(27)
-
75
8.19(289)
6.28(221)
2.81(99)
0.85(30)
-
80
8.91(314)
7.43(262)
4.96(175)
1.58(55)
-
85
9.51(335)
8.14(287)
5.91(208)
2.75(97)
0.95(33)
90
10.21(360)
8.76(309)
6.79(239)
3.41(120)
1.36(48)
95
10.83(382)
9.62(339)
8.11(286)
5.48(193)
2.61(92)
100
11.31(399)
10.55(372)
9.02(318)
6.12(216)
3.31(116)
105
11.84(418)
11.19(395)
9.99(352)
8.28(292)
5.32(187)
110
12.68(447)
11.88(419)
10.38(366)
9.16(323)
6.92(244)
115
13.19(465)
12.22(431)
11.55(407)
10.21(360)
8.23(290)
Static Pressure(mmAq (in.Aq))
Setting Value
0(0)
1(3.93)
2(7.87)
3(0.11)
4(0.15)
75
10.32(364)
7.68(271)
3.55(125)
-
-
80
11.06(390)
8.77(309)
4.71(166)
1.38(48)
-
85
11.84(418)
10.02(353)
6.95(245)
2.16(76)
-
90
12.73(449)
10.74(379)
8.26(291)
4.73(167)
1.25(44)
95
13.47(475)
12.13(428)
9.93(350)
6.74(238)
2.73(96)
100
14.16(500)
13.25(467)
10.51(371)
8.41(297)
3.65(128)
105
15.29(539)
14.11(498)
12.31(434)
9.83(347)
6.21(219)
110
16.09(568)
14.77(521)
13.49(476)
10.39(366)
8.32(239)
115
16.91(597)
15.88(560)
14.48(511)
12.77(450)
9.92(350)
120
17.81(628)
16.88(596)
15.15(535)
13.98(493)
10.85(383)
125
18.55(655)
17.84(630)
16.12(569)
15.13(534)
12.97(458)
130
19.01(671)
18.55(655)
17.33(612)
16.28(574)
14.59(515)
(Unit;cmm(cfm))
(Unit;cmm(cfm))