Installation Manual
13
ENGLISH
Installation
Pipe must be able to obtain the specified thickness and should be used with low
impurities.
Also when handling storage, pipe must be careful to prevent a fracture, deformity
and wound.
Should not be mixed with contaminations such as dust, moisture.
Plumbing materials and storage methods
Refrigerant piping on three principles
Drying Cleanliness
Airtight
Should be no moisture
inside
No dust inside.
There is no refrigerant
leakage
Items
Moisture
Dust
Leakage
Cause failure
- Significant hydrolysis of refrigerant
oil
- Degradation of refrigerant oil
- Poor insulation of the compressor
- Do not cold and warm
- Clogging of EEV, Capillary
- Degradation of refrigerant oil
- Poor insulation of the compressor
- Do not cold and warm
- Clogging of EEV, Capillary
- Gas shortages
- Degradation of refrigerant oil
- Poor insulation of the compressor
- Do not cold and warm
Countermeas
ure
- No moisture in the pipe
- Until the connection is completed,
the plumbing pipe entrance should
be strictly controlled.
- Stop plumbing at rainy day.
- Pipe entrance should be taken
side or bottom.
- When removal burr after cutting
pipe, pipe entrance should be
taken down.
- Pipe entrance should be fitted cap
when pass through the walls.
- No dust in the pipe.
- Until the connection is completed,
the plumbing pipe entrance should
be strictly controlled.
- Pipe entrance should be taken
side or bottom.
- When removal burr after cutting
pipe, pipe entrance should be
taken down.
- Pipe entrance should be fitted cap
when pass through the walls.
- Airtightness test should be.
- Brazing operations to comply with
standards.
- Flare to comply with standards.
- Flange connections to comply with
standards.