19
ENGLISH
Method of drawing out pipes on the bottom side
- Drawing out common pipe through side panel
Liquid pipe
No Use
(Weld with supplied accessory pipe cap)
Gas pipe
Remove Knock Out for the pipes
h
Please weld with the proper Low pressure Gas pipe included with
product.
Combination of Y
branch/header Method
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Header
Ⓕ
: Sealed piping
l
40 m [131 ft] (90m [295 ft])
h 40 m(
131
ft)
H 110 m [36
1
ft]
L 150 m [492 ft] (200 m [656 ft])
h
* : See Table 4
Y branch method
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Indoor Units
l
40 m [131 ft] (90m [295 ft])
h 40 m [131 ft]
H 110 m [36
1
ft]
L 150 m [492 ft] (200 m [656 ft])
Indoor
Unit
h
* : See Table 4
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch (Y branch)
Ⓒ
: Indoor Units
Ⓔ
: Connection branch
pipe between Outdoor
units: ARCNN41
Ⓕ
: Connection branch
pipe between Outdoor
units : ARCNN31
Ⓖ
: Connection branch
pipe between Outdoor
units : ARCNN21
Y branch method
Slave3
Slave2
Slave1
Master
Slave3
Indoor
Unit
Slave2
Slave1
Master
l
40 m [131 ft] (90m [295 ft])
H 110 m [36
1 ft]
L 150 m [492 ft] (200 m [656 ft])
h 40 m (131 ft)
10m or
less
ODU Capacity
Master ≥ Slave 1 ≥Slave 2 ≥Slave 3
h
* : See Table 4
Combination of Y branch/
header Method
Ⓐ
: Outdoor Unit
Ⓑ
: 1st branch(Y branch)
Ⓒ
: Y branch
Ⓓ
: Indoor Unit
Ⓔ
: Connection branch pipe
between Outdoor
units : ARCNN41
Ⓕ
: Connection branch pipe
between Outdoor
units : ARCNN31
Ⓖ
: Connection branch pipe
between Outdoor
units : ARCNN21
Ⓗ
: Header
Ⓘ
: Sealed piping
Slave3
Slave2
Slave1
Master
Slave3
Slave2
Slave1
Master
l
40 m [131 ft] (90m [295 ft]
H 110 m [36
1 ft]
L 150 m [492 ft] (200 m [656 ft])
h 40 m (
131
ft)
10m or
less
ODU Capacity
Master ≥ Slave 1 ≥Slave 2 ≥Slave 3
h
* : See Table 4
Header Method
Ⓐ
: Outdoor Unit
Ⓑ
: Header
Ⓒ
: Indoor Units
Ⓓ
: Sealed piping
Ⓔ
: Connection branch pipe
between Outdoor
units : ARCNN41
Ⓕ
: Connection branch pipe
between Outdoor
units : ARCNN31
Ⓖ
: Connection branch pipe
between Outdoor
units : ARCNN21
Slave3
Slave2
Slave1
Master
Slave3
Slave2
Slave1
Master
l
40 m [131 ft]
H 110 m [36
1 ft]
L 200 m [656 ft]
h 40 m (131 ft)
10m or
less
ODU Capacity
Master ≥ Slave 1 ≥Slave 2 ≥Slave 3
Series Outdoor Units (2 Units ~ 4 Units)
Header Method
Ⓐ
: Outdoor Unit
Ⓒ
: Indoor Units
Ⓓ
: Sealed piping
Ⓔ
: Header
l
40 m [131 ft]
h 40 m [131 ft]
H 110 m [36
1 ft]
L 200 m [656 ft]
Refrigerant piping system