48
ENGLISH
MAX. RPM Limit Setting
Chassis
UXA
UXB
Fan MAX. RPM
Limit (RPM)
oFF
880
1000
oP1
-20
-50
oP2
-40
-100
oP3
-60
-150
oP4
-80
-200
oP5
-100
-250
oP6
-120
-300
oP7
-140
-350
SLC(Smare Lode Control) Mode
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn14” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“oFF”,“op1”~“op3” Push the ‘
●
’ button
SLC(Smare Lode Control) Mode is set
Setting
Mode
Detail of function
oFF
Not Setting
-
oP1
Smooth Mode
Slowly control, a target pressure value
oP2
Normal Mode
Normal control, a target pressure value
oP3
Peak Mode
Fast control, a target pressure value
Mode setting
- on:using humidity sensor
- oFF:not setting
<Using of humidity sensor>
- When used cooling operation of SLC function,it will improve energy
effcience because evaporation temperature wll be decreased
- When used heating operation in case of high humidity condition,
deforest will be delayed because target high/low pressure will be
changed.
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn16” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“oFF”,“on” Push the ‘
●
’ button
Humidity Reference Control mode is set
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn16” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“Fn19” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“on”,“oFF” Push the ‘
●
’ button
Central Control Connection at Indoor
Unit side Mode is set
Compressor Input Current Limit
The current limits of each Compressor
Ex)16 A Set op6 >11.2 A
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“Func” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button :
“Fn20” Push the ‘
●
’ button
Select the Option using ‘
▶
’, ‘
◀
’ Button :
“oFF”,“op1”~”op10” Push the ‘
●
’ button
Compressor Input Current Limit mode is set
Mode
Compressor Input Current Limit
op1
95 %
op2
90 %
op3
85 %
op4
80 %
op5
75 %
op6
70 %
op7
65 %
op8
60 %
op9
55 %
op10
50 %
Compressor Input Current Limit
System Input Current Control
Mode setting method
Central Control Connection at Indoor Unit side
Mode setting method
Humidity Reference
Mode setting method
SLC (Smart Load Control)
Function for set the variable target pressure which for the high
efficiency and comport operation depend on ODU load.
Mode setting method