INSTALLATION
ENGLISH
9
Piping length and the elevation
Model
Pipe Size
mm(inch)
Length A(m)
Elevation B(m)
*Additional
refrigerant
(g/m)
Gas
Liquid
Standard
Max.
Standard
Max.
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
CAUTION
• Rated performance for refrigerant line length of:7.5m
• Capacity is based on standard length and maximum allowance length is on the basis of relia-
bility.
• Improper refrigerant charge may result in abnormal cycle.
!
LT-H282PLE0 15.88(5/8”) 6.35(1/4”)
7.5
50
5
30
25
LT-H332NLE0 15.88(5/8”) 6.35(1/4”)
7.5
50
5
30
45
LT-H452MLE0 19.05(3/4”) 9.52(3/8”)
7.5
50
5
30
45
LT-H512MLE0 19.05(3/4”) 9.52(3/8”)
7.5
50
5
30
50
LT-C282PLE0 15.88(5/8") 6.35(1/4")
7.5
50
5
30
30
LT-C332NLE0 15.88(5/8") 6.35(1/4")
7.5
50
5
30
30
LT-C452MLE0 19.05(3/4") 9.52(3/8")
7.5
50
5
30
55
LT-C512MLE0 19.05(3/4") 9.52(3/8")
7.5
50
5
30
55
LT-C48BMLE0 19.05(3/4”) 9.52(3/8”)
7.5
50
5
30
50
LT-C52BMLE0 19.05(3/4”) 9.52(3/8”)
7.5
50
5
30
50