Electric characteristics
6RMI0-04C
48
Inverter Single
9. Electric characteristics
Notes :
1. Voltage range
Voltage supplied to the unit terminals should be within the
minimum and maximum range
2. Maximum allowable voltage unbalance between phase is 2 %
3. Select wire spec. based on the larger value of MCA.
4. RLA is measured during each individual compressor test
condition.
5. OFM is measured as the outdoor unit test condition
6. Recommended circuit breaker is ELCB (Earth Leakage circuit
breaker)
MCA : Minimum Circuit Amperes (A)
MOP : Maximum rating over current protective device.(A)
MSC : Maximum Starting Current)(A)
RLA : Rated Load Amperes (A)
OFM : Outdoor Fan Motor
kW : Fan Motor rated output (kW)
FLA : Full Load Amperes (A)
Unit
Power
Compressor
OFM
Model
Type
Hz
Voltage
Voltage range MCA
MOP
MSC
RLA
kW
FLA
ASUW093F2B2(LAU090HVP)
Inverter
60
208~230
MIN : 187
MAX : 253
10
15
-
7.6
0.08
0.25
ASUW123F2B2(LAU120HVP)
10
15
-
7.6
0.08
0.25
ASUW093MMM9(LSU090HYV)
10
15
-
7.6
0.12
1.04
ASUW123MMM9(LSU120HYV)
10
15
-
7.6
0.12
1.04
ASUW093BRM9(LAU090HSV2)
10
15
-
7.6
0.08
0.45
ASUW123BRM9(LAU120HSV2)
10
15
-
7.6
0.08
0.45
ASUW183CRM9(LAU180HSV2)
19
30
-
14.6
0.12
0.75
ASUW243CRM9(LAU240HSV2)
19
30
-
14.6
0.12
0.75
ASUW093B1Y9(LSU091HSV2)
10
15
-
7.6
0.08
0.25
ASUW123B1Y9(LSU121HSV2)
10
15
-
7.6
0.08
0.25
ASUW183C2Y9(LSU181HSV2)
19
30
-
14.6
0.12
0.25
ASUW243DGY9(LSU240HSV2)
19
30
-
14.6
0.12
0.75
ASUW303DGY9(LSU307HV2)
19
30
-
14.6
0.12
0.75
ASUW363DGY9(LSU360HV2)
19
30
-
14.6
0.12
0.75